Modbus Communications and Connectivity
22
5.4.2 Function Code Support
The OpenComms NIC implements the following Modbus functions. 
However, integrators will use function code 0x03, and 0x06 most often 
due to the type of data to be acquired.
5.4.3 Read/Write Holding Registers (0x03, 0x06, 0x10)
A holding register is a 16-bit message unit. In principle, a message in 
a holding register is write / readable, but holding registers can be used 
by read-only data as well. Holding registers are mapped into 
40001-49999 logic address range.
Holding registers can be read by function code 0x03. A maximum of 
125 registers can be read by a single query.
Function code 0x06 requests the server to change the content of a sin-
gle holding register, and function code 0x10 requests server to change 
the contents of multiple holding registers adjacent to each other.
5.4.4 Read Input Registers (0x04)
The input register block contains read-only data accessible to the user. 
A datum in the input register block occupies one or multiple registers 
such as described in the previous section. The input registers are 
mapped into 30000-39999 of the logic address range.
Up to 125 input registers can be read by a single query using function 
code 0x04.
5.4.5 Read, Set Coil Status (0x01, 0x05, 0x0F)
Coil status contains bit-mapped status accessible to the users. In prin-
ciple, a coil status can be read, set or cleared by the host client. Multi-
ple coil status can be read by specifying the index of bits of the first 
coil and the number of consecutive coils in a single query.
Coil status can be read by function code 0x01.
Function code 0x05 set or clear a single coil, and function code 0x0F 
set or clear multiple coils.
0x01
Read Coil Status
0x02
Read Input Status
0x03
Read Holding Registers
0x04
Read Input Registers
0x06
Write Single Holding Register
0x0F
Force Multiple Coils
0x10
Preset Multiple Holding Registers