Emerson FPC Manuel D’Utilisation

Page de 40
Installation Instructions
22
Figure 16 Typical control wiring for units with monitoring
F
a
ct
o
ry-
S
u
pp
lie
d W
ir
in
g
24VDC W204
Summary Alarm N.O. W208
Summary Alarm N.C. W207
N.O. REPO W205
Summary Alarm Com. W206
REPO Com. W203
N.C. REPO       W202
24VDC       W201
Summary 
Alarm Output
S
N.O. REPO
N.C. REPO
Remove jumper 
when Normally 
Closed (N.C.) 
REPO is used
GRN
BLK
WHT
Low Voltage 
Terminal Strip
Building 
Interface 
Relay
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
4th Customer Alarm W213
Summary Alarm N.O. W208
1st Customer Alarm W210
2nd Customer Alarm W211
3nd Customer Alarm W212
5th Customer Alarm W214
RS-232 COM (BLK)
RS-232 RXD (WHT)
RS-232 TXD (RED)
Comm Cable-(BLK)
Comm Cable+(RED)
To 
SiteScan
System
Remove jumper 
when fifth customer 
alarm is used
Optional 
customer 
alarm 
inputs
R
7
A
B
9
6
3
1
4
NOTES
1. All switching devices are to be suitable for switching low current 24VDC. Minimum 
recommended wire size is 18AWG stranded copper with 300V insulation.
All wiring and devices are field-supplied except where noted.
See installation manual for detailed installation procedures.
2. Low voltages terminal strip may be located in unit or low voltage control junction box.
3. The total load on the 24VDC supply (both N.O. and N.C. REPO circuits) must be limited to 1A.
4. Multiple normally open (N.O.) REPO switches may be paralleled.
Multiple normally closed (N.C.) REPO switches may be connected in series. All lamps (if used) 
are connected in parallel.
5. The summary alarm contacts are rated for 0 to 30VAC or VDC, 0.5A, 10W maximum.
6. Customer alarms 1 through 4 are normally open (indicates alarm on contact closure). Customer 
alarm 5 is normally closed (indicates alarm on contact opening).
7. RS-232 communication port is connected to the low voltage terminal strip inside unit only. 
Connect using suitable 300V communication cable.