Emerson FPC Manuel D’Utilisation

Page de 40
Equipment Inspection and Startup
24
Table 11
Torque specifications, general
Electrical connections
with 1 Belleville washer
Electrical connections
with 2 Belleville washers
Torque
Torque
lb-in
N-m lb-in
N-m 
Bolt shaft size, in./mm
1/4 / M6
40
4.5
80 
9.0 
5/16 / M8
80
9.0
180 
18.0 
3/8 / M10
120
13.6
240 
27.1 
1/2 / M12
480
54.3
Input and output breakers
Up to 150 amp
80
9.0
160 
18.0 
175 - 500A
120
13.6
240 
27.1 
Table 12
Panelboard main circuit breaker torque specifications
Torque
lb-in
N-m 
Busbar-to-breaker 240 27.1 
Table 13
Branch circuit breaker torque specifications
Breaker size 
lb-in
N-m 
Up to 30 amp
20
4.0
40 to 100 amp
20
5.1
Table 14
Terminal block compression lug torque specifications
AWG wire size
or range 
Torque
lb-in
N-m 
#14 - #10
35
4.0
#8
40
4.5