Emerson ITR Manuel D’Utilisation

Page de 74
Electrical Data
46
Table 20
Outdoor condensing units—Quiet-Line
Electrical Data 60 Hz, Quiet-Line, 95°F (35°C) 
Voltage
Model
PFHZ67A-_L
208/230-3-60
FLA
 21.1
WSA
 25.9
OPD
 45.0
380-3-60
FLA
 12.5
WSA
 15.2
OPD
 25.0
460-3-60
FLA
 10.9
WSA
 13.4
OPD
 20.0
575-3-60
FLA
8.8
WSA
 10.8
OPD
 15.0
Table 21
Indoor condensing units, air-cooled *
Electrical Data 60 Hz 95°F (35°C) Ambient
Voltage
Model
MC_65A
208/230-3-60
FLA
26.5
WSA
31.7
OPD
50.0
460-3-60
FLA
12.9
WSA
15.4
OPD
25.0
575-3-60
FLA
9.7
WSA
11.6
OPD
15.0
* Contact factory for 380-3-60 data.
Table 22
Indoor condensing units, water-cooled *
Voltage
Model
MC_69W
208/230-3-60
FLA
20.7
WSA
25.9
OPD
45.0
460-3-60
FLA
10.0
WSA
12.5
OPD
20.0
575-3-60
FLA
7.4
WSA
9.3
OPD
15.0
* Contact factory for 380-3-60 data.