Emerson ITR Manuel D’Utilisation

Page de 74
Electrical Data
48
Table 27
Liebert Challenger ITR electrical data—50 Hz
Model Type
Self-Contained
Split System Evaporator or Chilled Water
B*065A, 070WG, 058G
B*059E, 101C
3 Phase, 50Hz
Voltage
200
230
380/415
200
 230
380/415
With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note: See Table 28 for units w/SCR reheats.
1
)
Motor
1.1 kW (1.5 hp)
1.1 kW (1.5 hp)
FLA
66.0
64.4
34.4
58.1
54.8
30.8
Motor
1.5 kW (2.0 hp)
1.5 kW (2.0 hp)
FLA
67.7
65.9
35.2
59.8
56.3
31.6
Motor
2.2 kW (3.0 hp)
2.2 kW (3.0 hp)
FLA
70.8
68.6
36.8
62.9
59.0
33.2
Humidifier Only (Infrared or Steam Generating)
Motor
1.1 kW (1.5 hp)
1.1 kW (1.5 hp)
FLA
38.8
36.4
19.1
18.1
15.7
9.1
Motor
1.5 kW (2.0 hp)
1.5 kW (2.0 hp)
FLA
40.5
37.9
19.9
19.8
17.2
9.9
Motor
2.2 kW (3.0 hp)
2.2 kW (3.0 hp)
FLA
43.6
40.6
21.5
22.9
19.9
11.5
Electric Reheat Only (Note: See Table 28 for units w/SCR reheats.
1
)
Motor
1.1 kW (1.5 hp)
1.1 kW (1.5 hp)
FLA
66.0
64.4
34.4
45.3
43.7
24.4
Motor
1.5 kW (2.0 hp)
1.5 kW (2.0 hp)
FLA
67.7
65.9
35.2
47.0
45.2
25.2
Motor
2.2 kW (3.0 hp)
2.2 kW (3.0 hp)
FLA
70.8
68.6
36.8
50.1
47.9
26.8
Without Electric Reheat and Humidifier
Motor
1.1 kW (1.5 hp)
1.1 kW (1.5 hp)
FLA
26.0
25.3
12.7
5.3
4.6
2.7
Motor
1.5 kW (2.0 hp)
1.5 kW (2.0 hp)
FLA
27.7
26.8
13.5
7.0
6.1
3.5
Motor
2.2 kW (3.0 hp)
2.2 kW (3.0 hp)
FLA
30.8
29.5
15.1
10.1
8.8
5.1
1. For Split System Evaporators with SCR reheat, use the values above.
FLA = Full Load Amps (Input Amps)
RLA = Rated Load Amps
LRA = Locked Rotor Amps
* R = In The Row; M = In The Row with Econ-O-Coil