Electrical Data
47
Table 23
Fan speed control condensers *
95°F (35°C) Ambient, 1 Phase - 60 Hz
CSF104
Voltage
208/230
460
575
FLA
4.8
2.5
1.9
WSA
6.0
3.1
2.4
OPD
15.0
15.0
15.0
* Contact factory for 380-3-60 data.
Table 24
Liebert Lee-Temp condensers *
95°F (35°C) Ambient, 3 Phase - 60 Hz
CSL104
Voltage
208/230
460
575
FLA
3.5
1.7
1.4
WSA
4.4
2.1
1.8
OPD
15.0
15.0
15.0
* Contact factory for 380-3-60 data.
Table 25
Liebert Lee-Temp receiver heater pads for use w/CSL condensers
Volts
120
230
Watts/Pad
150
150
FLA
1.4
0.7
WSA
1.8
0.9
OPD
15
15
Separate electrical source required for continuous operation 
of single phase heater pads for Liebert Lee-Temp.
Table 26
Drycooler and pump package - 95°F (35°C) ambient *
Voltage
208/230
460
575
Glycol
DSF Model
112
112
112
Pump Hp
3/4
3/4
3/4
FLA
7.0
3.3
2.7
WSA
7.9
3.7
3.1
OPD
15
15.0
15.0
Glycol DS0174
DSF Model
174
174
174
Pump Hp
1.5
1.5
1.5
FLA
13.6
6.4
5.2
WSA
15.3
7.2
5.8
OPD
20
15.0
15.0
GLYCOOL
DSO Model
112
112
112
Pump Hp
1-1/2 
1-1/2
 1-1/2
FLA
10.1
4.7
 3.8
WSA
11.8
 5.5 
4.4
OPD
15
15
15
1. Pump and drycooler powered from same 3 phase feeder.