Configuration Overview
10
3.5
Open the Web Interface
To access configuration using the Web interface:
1. Open a Web browser such as Internet Explorer, then enter 
the IP address or hostname of the Web card in the address 
bar—e.g., http://192.168.0.125.
2. Click on the Configure tab, shown at right. Configuration 
Categories appear in the left panel, organized with folder 
icons.
3. Click on any configuration category, and the Connect To 
box opens.
4. Enter the Administrator username and password (both 
case-sensitive):
a. User Name (default is Liebert)
b. Password (default is Liebert)
5. Click OK.
6. Refer to 3.1 - Guide to Configuration for details on each 
function.
7. After making changes, click the Save button, then click on 
Reinitialize to reboot the Web card and put your changes 
3.6
Saving Changes and Reinitializing the Web Card
Follow the applicable steps for your interface to save configuration changes and reinitialize the Web 
card. Changes will not take effect until these steps are completed.
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
• After each change is made, a reminder appears (shown at right).
• Return to the Main Menu, then choose Exit and Save. A mes-
sage appears and remains until the card is reinitialized, followed 
by a message that the process was successful.
Web Interface
• After making each change, click the Save button. A reminder 
appears each time you make a change (shown at right).
• Without leaving the Configure tab window (below left), click 
Reinitialize in the left panel, then click the Reinitialize button 
at right to reboot the Web card and put your changes into effect.
• A message window appears, shown above right, and remains until the card is reinitialized.
NOTE
For security, change the default username and 
Configuration
Categories
Configure tab
Connect To
Reinitialize
(to save any changes)
New Settings will take effect
when saved
GO TO MAIN MENU AND DO 'EXIT AND
SAVE' TO SAVE YOUR CHANGES!
Exiting and saving...
Configuration saved successfully
First click
Reinitialize
at left
Then click
Reinitialize
button
Progress message window