Configuring the Discrete Batch Application
B.5
Performing Batch AOC calibration
Batch AOC (Automatic Overshoot Compensation) keeps the actual quantity delivered as close as
possible to the batch target, by minimizing the amount of overshoot.
possible to the batch target, by minimizing the amount of overshoot.
If batch AOC is enabled (see Section B.3.2), batch AOC calibration is required to provide data for the
compensation process. Thereafter, batch AOC calibration is recommended:
compensation process. Thereafter, batch AOC calibration is recommended:
•
Whenever consistent overshooting or undershooting of the target occurs
•
If equipment (valve or pump) is changed
Note: If batch AOC is not enabled, you cannot perform batch AOC calibration.
To perform batch AOC calibration using ProLink II:
1. In the
File
menu, click on
Calibration
.
2. Click on
AOC calibration
.
3. Press the
Start Calibration
button. The
AOC Calibration Active
light turns red, and will
remain red while batch AOC calibration is in progress.
4. Run 2–10 batches.
5. When overshoot has been adequately minimized, press the
Save Calibration
button.