Emerson Network Router Manuel D’Utilisation

Page de 110
Installation and Use Manual
97
Configuring the Discrete Batch Application
In
de
x
 
 
Discre
te Batc
h
In
de
x
 
 
Discre
te Batc
h
In
de
x
 
 
Discre
te Batc
h
In
de
x
 
 
Discre
te Batc
h
If the batch totalizer is inhibited while a batch is running:
And  the 
No-flow timeout
 batch control option (see Section B.3.2) is set to 0, no timeout alarm 
will be posted.
And  the 
No-flow timeout
 batch control option is set to a non-zero value, a timeout alarm will 
be posted if the timeout period expires before batch totalizing resumes.
B.4
Running a batch
The ProLink II 
Batcher Control
 window, shown in Figure B-4, can be used for batch operation. It 
provides the same functionality as the batch process screen on the transmitter display.
Figure B-4
Batcher Control window
Batch management functions are shown at the top of the window:
To specify the preset to use for batching, select it from the dropdown list at the top of the 
Batcher Control window, and click 
Apply
.
The current target is displayed. Depending on the setting of 
Lockout target
, you may or may 
not be able to change the value from this screen. To change it, enter the new target value and 
click 
Apply
.
To inhibit batch or inhibit batch totalizer, check the checkboxes and click 
Apply
. For a 
discussion of these functions, see the preceding section.
To reset, start, stop, resume, and end a batch, use the batch control buttons. These functions 
may also be assigned to a discrete event or discrete input (see Section B.3.4). For a definition 
of these functions, see Table B-4.
Status of the batch application is shown at the bottom of the window. A red light indicates that the 
associated condition is active.