ProLink
®
 II Software for Micro Motion
®
 Transmitters
Configuring the Discrete Batch Application
Inhibit Batch and Inhibit Totalizer processing
If the Inhibit Batch function is mapped to a discrete input:
When that discrete input is in the active state:
-
A batch cannot be started.
-
A Start Not Okay alarm is posted if starting a batch is attempted.
If the discrete input then becomes inactive, the batch does not start automatically.
If a batch is already running when the discrete output becomes active, the batch is not affected.
If the Inhibit Totalizer function is mapped to a discrete input:
The totalizer will not increment while the discrete input is active.
The totalizer will resume incrementing automatically when the discrete input becomes 
inactive.
If the discrete input is inactive, the totalizer is active, whether or not a batch is running. Even if 
a batch is not running, the totals will be incremented if flow is detected.
Table B-4
Batch control assignments
Function
Default 
assignment
Assignment options
ON state actions
End discrete 
batch
None
Specify the method that will 
be used to perform the batch 
control function:
• None
• Discrete input 1
• Discrete input 2
• Discrete event 1
• Discrete event 2
• Discrete event 3
• Discrete event 4
• Discrete event 5
• Ends the batch.
• The batch cannot be resumed.
• The batch totalizer must be reset for the next 
batch.
Inhibit discrete 
batch
• Batch cannot be started.
• Inhibit batch is used for temporary lockout. See 
Inhibit discrete 
batch totalizer
• Delivers the batch but does not totalize.
• Inhibit totalizer is used when process fluid is 
recirculated. See Section .
Reset discrete 
batch
• Resets batch total to zero.
• Batch reset cannot be performed while a batch is 
running or while a batch is stopped. Before a 
batch can be reset, the batch target must be 
reached or the batch must be ended.
• The batch controller can be configured to reset 
automatically on start. To configure Reset on 
start, see Section B.3.2.
Resume discrete 
batch
• Resumes a batch that has been stopped.
• Counting resumes from the total at which the 
batch was stopped.
Start discrete 
batch
Starts the batch by opening the flow control valve(s) 
and/or starting the pump.
Stop discrete 
batch
• Stops the batch.
• The batch can be resumed if the batch total is 
less than the batch target.
• If lockout target is disabled as a control option, the 
operator can change the target before resuming.
• To enable or disable lockout target, see 
Increment 
current batch 
preset
Selects next configured preset (as listed in the 
preset menus) for use in the next batch.