Configuring the Discrete Batch Application
One-stage versus two-stage batching
If 
Number of stages
 is set to 1, a single pump or valve is used to control the batch. When the batch is 
started, the pump starts or the valve opens; at the configured target, the pump stops or the valve 
closes. 
Open primary
Open secondary
, and 
Close primary
 values are not required when 
configuring the preset (see Section B.3.3).
If 
Number of stages
 is set to 2, two valves are used to control the batch, and the following 
requirements apply when configuring the preset:
Both 
Open primary
 and 
Open secondary
 must be configured.
Either 
Open primary
 or 
Open secondary
 must be set to 0. Both may be set to 0 if desired.
Close primary
 must be configured.
B.3.3
Configure presets
You can configure up to six batch presets. Preset 1 cannot be disabled, but you can change its 
configuration.
Table B-3 defines the options for configuring presets. To configure a preset, first select the preset to be 
configured, then define its parameters.
Table B-3
Preset parameters
Setting
Default
Description
Name
• Preset 1
• Preset 2
• Preset 3
• Preset  4 
• Preset 5
• Preset 6
• Enter the name that will appear on operation screens and in preset selection 
menus. 
• A maximum of 22 characters can be stored. 
Enable preset
• Yes for preset 1
• No for presets 2-6
• If set to Yes, the batch preset can be selected for use. See Section B.4.
• If set to No, the batch preset is disabled and cannot be selected.
• Preset 1 cannot be disabled.
Open primary
(1)
0.00% of target or
0.0 kg quantity
• Enter the quantity or the percent of the target at which the primary valve will 
open. See the examples later in this section.
• Either Open primary or Open secondary must be set to 0. If one of these 
parameters is set to a non-zero value, the other is set to 0 automatically
• Before a batch can be started, the primary valve must be assigned to a 
discrete output. See Section B.3, Step 3.
Open 
secondary
0.00% of target or
0.0 kg quantity
• Enter the quantity or the percent of the target at which the secondary valve 
will open. See the examples later in this section.
• Either Open primary or Open secondary must be set to 0. If one of these 
parameters is set to a non-zero value, the other is set to 0 automatically
• Before a batch can be started, the secondary valve must be assigned to a 
discrete output. See Section B.3, Step 3.
Close primary
80.00% of target or
0.0 kg quantity
• Enter the quantity subtracted from the target, or the percent of the target, at 
which the primary valve will close. See the examples later in this section.
• The secondary valve always closes when the target is achieved.
• Before a batch can be started, the primary valve must be assigned to a 
discrete output. See Section B.3, Step 3.
End warning
(2)
80.00% of target or
0.0 kg quantity
• If End warning is enabled as a control option, enter the quantity subtracted 
from the target, or the percent of the target, at which the end warning will 
occur. See the examples later in this section.
• End warning can be assigned to a discrete output, using the Discrete IO 
panel in the ProLink II Configuration window.