Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
283
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 94
Liebert XDP
, Liebert XDC
 - Multistate Data
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
External Air
Ext Air Sensor A Over Temp - Event Control
Multistate_Value
1
4602_1
RW
1 = Disabled
2 = Enabled
Ext Air Sensor A Over Temp - Event Type
Multistate_Value
2
4603_1
RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor B Over Temp - Event Control
Multistate_Value
3
4605_1
RW
1 = Disabled
2 = Enabled
Ext Air Sensor B Over Temp - Event Type
Multistate_Value
4
4606_1
RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor A Under Temp - Event Control
Multistate_Value
5
4609_1
RW
1 = Disabled
2 = Enabled
Ext Air Sensor A Under Temp - Event Type
Multistate_Value
6
4610_1
RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor B Under Temp - Event Control
Multistate_Value
7
4612_1
RW
1 = Disabled
2 = Enabled
Ext Air Sensor B Under Temp - Event Type
Multistate_Value
8
4613_1
RW
1 = Message
2 = Warning
3 = Alarm
Ext Dew Point Over Temp - Event Control
Multistate_Value
9
4616_1
RW
1 = Disabled
2 = Enabled
Ext Dew Point Over Temp - Event Type
Multistate_Value
10
4617_1
RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor A Issue - Event Control
Multistate_Value
11
4619_1
RD
1 = Disabled
2 = Enabled
Ext Air Sensor A Issue - Event Type
Multistate_Value
12
4620_1
RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor B Issue - Event Control
Multistate_Value
13
4622_1
RD
1 = Disabled
2 = Enabled
Ext Air Sensor B Issue - Event Type
Multistate_Value
14
4623_1
RW
1 = Message
2 = Warning
3 = Alarm
Chilled Water
Supply CW Over Temp - Event Control
Multistate_Value
25
4627_1
RD
1 = Disabled
2 = Enabled
Supply CW Over Temp - Event Type
Multistate_Value
26
4628_1
RW
1 = Message
2 = Warning
3 = Alarm
Supply CW Temp Sensor Issue - Event Control
Multistate_Value
27
4630_1
RD
1 = Disabled
2 = Enabled
Supply CW Temp Sensor Issue - Event Type
Multistate_Value
28
4631_1
RW
1 = Message
2 = Warning
3 = Alarm
Chilled Water Cntrl Valve Pos - Event Control
Multistate_Value
29
4704_1
RW
1 = Disabled
2 = Enabled
Chilled Water Cntrl Valve Pos - Event Type
Multistate_Value
30
4705_1
RW
1 = Message
2 = Warning
3 = Alarm