Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
284
Refrigerant
Supply Refrig Over Temp - Event Control
Multistate_Value
41
4635_1
RD
1 = Disabled
2 = Enabled
Supply Refrig Over Temp - Event Type
Multistate_Value
42
4636_1
RW
1 = Message
2 = Warning
3 = Alarm
Supply Refrig Under Temp - Event Control
Multistate_Value
43
4638_1
RD
1 = Disabled
2 = Enabled
Supply Refrig Under Temp - Event Type
Multistate_Value
44
4639_1
RW
1 = Message
2 = Warning
3 = Alarm
Supply Refrig Temp Sensor Issue - Event Control Multistate_Value
45
4641_1
RD
1 = Disabled
2 = Enabled
Supply Refrig Temp Sensor Issue - Event Type
Multistate_Value
46
4642_1
RW
1 = Message
2 = Warning
3 = Alarm
Fluid
Supply Fluid Over Temp - Event Control
Multistate_Value
57
4646_1
RD
1 = Disabled
2 = Enabled
Supply Fluid Over Temp - Event Type
Multistate_Value
58
4647_1
RW
1 = Message
2 = Warning
3 = Alarm
Supply Fluid Under Temp - Event Control
Multistate_Value
59
4649_1
RD
1 = Disabled
2 = Enabled
Supply Fluid Under Temp - Event Type
Multistate_Value
60
4650_1
RW
1 = Message
2 = Warning
3 = Alarm
Supply Fluid Temp Sensor Issue - Event Control
Multistate_Value
61
4652_1
RD
1 = Disabled
2 = Enabled
Supply Fluid Temp Sensor Issue - Event Type
Multistate_Value
62
4653_1
RW
1 = Message
2 = Warning
3 = Alarm
Pumps
Pump 1 State
Multistate_Value
73
4654_1
RD
1 = Off / 2 = On
Pump 2 State
Multistate_Value
74
4655_1
RD
1 = Off / 2 = On
Pump 1 Loss of Flow - Event Control
Multistate_Value
75
4657_1
RW
1 = Disabled
2 = Enabled
Pump 1 Loss of Flow - Event Type
Multistate_Value
76
4658_1
RW
1 = Message
2 = Warning
3 = Alarm
Pump 2 Loss of Flow - Event Control
Multistate_Value
77
4660_1
RW
1 = Disabled
2 = Enabled
Pump 2 Loss of Flow - Event Type
Multistate_Value
78
4661_1
RW
1 = Message
2 = Warning
3 = Alarm
Pump Short Cycle - Event Control
Multistate_Value
79
4663_1
RD
1 = Disabled
2 = Enabled
Pump Short Cycle - Event Type
Multistate_Value
80
4664_1
RW
1 = Message
2 = Warning
3 = Alarm
Table 94
Liebert XDP
, Liebert XDC
 - Multistate Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes