Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
285
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Compressors
Compressor 1A State
Multistate_Value
91
4665_1
RD
1 = Off / 2 = On
Compressor 1B State
Multistate_Value
92
4666_1
RD
1 = Off / 2 = On
Compressor 2A State
Multistate_Value
93
4667_1
RD
1 = Off / 2 = On
Compressor 2B State
Multistate_Value
94
4668_1
RD
1 = Off / 2 = On
Compressor 1A High Head Pressure - Event 
Control
Multistate_Value
95
4670_1
RW
1 = Disabled
2 = Enabled
Compressor 1A High Head Pressure - Event 
Type
Multistate_Value
96
4671_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 1B High Head Pressure - Event 
Control
Multistate_Value
97
4673_1
RW
1 = Disabled
2 = Enabled
Compressor 1B High Head Pressure - Event 
Type
Multistate_Value
98
4674_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2A High Head Pressure - Event 
Control
Multistate_Value
99
4676_1
RW
1 = Disabled
2 = Enabled
Compressor 2A High Head Pressure - Event 
Type
Multistate_Value
100
4677_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2B High Head Pressure - Event 
Control
Multistate_Value
101
4679_1
RW
1 = Disabled
2 = Enabled
Compressor 2B High Head Pressure - Event 
Type
Multistate_Value
102
4680_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 1A Short Cycle - Event Control
Multistate_Value
103
4682_1
RW
1 = Disabled
2 = Enabled
Compressor 1A Short Cycle - Event Type
Multistate_Value
104
4683_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 1B Short Cycle - Event Control
Multistate_Value
105
4685_1
RW
1 = Disabled
2 = Enabled
Compressor 1B Short Cycle - Event Type
Multistate_Value
106
4686_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2A Short Cycle - Event Control
Multistate_Value
107
4688_1
RW
1 = Disabled
2 = Enabled
Compressor 2A Short Cycle - Event Type
Multistate_Value
108
4689_1
RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2B Short Cycle - Event Control
Multistate_Value
109
4691_1
RW
1 = Disabled
2 = Enabled
Compressor 2B Short Cycle - Event Type
Multistate_Value
110
4692_1
RW
1 = Message
2 = Warning
3 = Alarm
Circuit 1 Low Suction Pressure - Event Control
Multistate_Value
111
4694_1
RW
1 = Disabled
2 = Enabled
Circuit 1 Low Suction Pressure - Event Type
Multistate_Value
112
4695_1
RW
1 = Message
2 = Warning
3 = Alarm
Circuit 2 Low Suction Pressure - Event Control
Multistate_Value
113
4697_1
RW
1 = Disabled
2 = Enabled
Table 94
Liebert XDP
, Liebert XDC
 - Multistate Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes