BACnet Communications - UPS Systems
307
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
PowerModule 1
Power Module Fan Fault 
Binary_Value
99
5838_1
RD
Active on Alarm
Power Module Over Temperature 
Binary_Value
100
5839_1
RD
Active on Alarm
Power Module Shutdown - Over Temperature 
Binary_Value
101
5840_1
RD
Active on Alarm
PowerModule 2
Power Module Fan Fault 
Binary_Value
112
5838_2
RD
Active on Alarm
Power Module Over Temperature 
Binary_Value
113
5839_2
RD
Active on Alarm
Power Module Shutdown - Over Temperature 
Binary_Value
114
5840_2
RD
Active on Alarm
PowerModule 10
Power Module Fan Fault 
Binary_Value
216
5838_10
RD
Active on Alarm
Power Module Over Temperature 
Binary_Value
217
5839_10
RD
Active on Alarm
Power Module Shutdown - Over Temperature 
Binary_Value
218
5840_10
RD
Active on Alarm
BatteryModule 1
Battery Module Temperature Sensor Fault 
Binary_Value
229
5847_1
RD
Active on Alarm
Battery Module Over Temperature 
Binary_Value
230
5848_1
RD
Active on Alarm
Replace Battery Module 
Binary_Value
231
5849_1
RD
Active on Alarm
BatteryModule 2
Battery Module Temperature Sensor Fault 
Binary_Value
242
5847_2
RD
Active on Alarm
Battery Module Over Temperature 
Binary_Value
243
5848_2
RD
Active on Alarm
Replace Battery Module 
Binary_Value
244
5849_2
RD
Active on Alarm
BatteryModule 80
Battery Module Temperature Sensor Fault 
Binary_Value
1256
5847_80
RD
Active on Alarm
Battery Module Over Temperature 
Binary_Value
1257
5848_80
RD
Active on Alarm
Replace Battery Module 
Binary_Value
1258
5849_80
RD
Active on Alarm
ChargerModule
Charger Module Fan Fault 
Binary_Value
1269
5842_1
RD
Active on Alarm
Table 102 Liebert APS
 - Binary Data (continued)
Data Label
Object Type
Instance
Object
Name
Access
Notes