Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
308
Table 103 Liebert APS
 - 
Analog
 Data
Data Label
Object Type
Instance
Object Name
Access
Notes
Input
System Input RMS L1-N
Analog_Value
1
4096_1
RD
Units: VAC 
System Input RMS L2-N
Analog_Value
2
4098_1
RD
Units: VAC 
System Input RMS L3-N
Analog_Value
3
4100_1
RD
Units: VAC 
System Input RMS L1-L2 
Analog_Value
4
4097_1
RD
Units: VAC 
System Input RMS L2-L3 
Analog_Value
5
4099_1
RD
Units: VAC 
System Input RMS L3-L1 
Analog_Value
6
4101_1
RD
Units: VAC 
System Input RMS Current L1 
Analog_Value
7
4113_1
RD
Units: A AC 
System Input RMS Current L2 
Analog_Value
8
4114_1
RD
Units: A AC 
System Input RMS Current L3 
Analog_Value
9
4115_1
RD
Units: A AC 
System Input Frequency 
Analog_Value
10
4105_1
RD
Units: Hz 
System Input Power Factor L1 
Analog_Value
11
4116_1
RD
System Input Power Factor L2 
Analog_Value
12
4117_1
RD
System Input Power Factor L3 
Analog_Value
13
4118_1
RD
System Input Brown Out Count 
Analog_Value
14
4119_1
RD
System Input Black Out Count 
Analog_Value
15
4120_1
RD
Bypass
Bypass Input Voltage RMS L1-N 
Analog_Value
26
4128_1
RD
Units: VAC 
Bypass Input Voltage RMS L2-N 
Analog_Value
27
4129_1
RD
Units: VAC 
Bypass Input Voltage RMS L1-L2 
Analog_Value
28
4125_1
RD
Units: VAC 
Bypass Input Frequency 
Analog_Value
29
4131_1
RD
Units: Hz 
Number Of Transfers To Bypass 
Analog_Value
30
5837_1
RD
Battery
Battery Time Remaining 
Analog_Value
41
4150_1
RD
Units: min 
Battery Volts for Cabinet 
Analog_Value
42
4155_1
RD
Units: VDC 
DC Bus Current 
Analog_Value
43
4149_1
RD
Units: A DC 
Battery Percentage Charge 
Analog_Value
44
4153_1
RD
Units: % 
Battery Temperature 
Analog_Value
45
5853_1
RD
Units: deg C 
Battery Temperature 
Analog_Value
10045
5853_1_deg_F
RD
Units: deg F 
Number of Discharge Cycles 
Analog_Value
46
5854_1
RD
Accumulated Discharge Time 
Analog_Value
47
5855_1
RD
Units: hr 
Time Until Next Auto Battery Test 
Analog_Value
48
5804_1
RD
Units: min 
Number of EBC Installed 
Analog_Value
49
5800_1
RD
Low Battery Warning Time 
Analog_Value
50
5802_1
RW
Units: min 
Output
System Output Voltage RMS L1-N 
Analog_Value
61
4385_1
RD
Units: VAC 
System Output Voltage RMS L2-N 
Analog_Value
62
4386_1
RD
Units: VAC 
System Output Voltage RMS L1-L2 
Analog_Value
63
4201_1
RD
Units: VAC 
System Output RMS Current L1 
Analog_Value
64
4204_1
RD
Units: A AC 
System Output RMS Current L2 
Analog_Value
65
4205_1
RD
Units: A AC 
System Output Frequency 
Analog_Value
66
4207_1
RD
Units: Hz 
System Output Power Factor L1 
Analog_Value
67
4210_1
RD
System Output Power Factor L2 
Analog_Value
68
4211_1
RD
System Output Apparent Power 
Analog_Value
69
4209_1
RD
Units: kVA 
System Output Apparent Power L1 
Analog_Value
70
5868_1
RD
Units: kVA