Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
309
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
System Output Apparent Power L2
Analog_Value
71
5869_1
RD
Units: kVA 
System Output Power
Analog_Value
72
4208_1
RD
Units: kW 
System Output Power L1
Analog_Value
73
5859_1
RD
Units: kW 
System Output Power L2 
Analog_Value
74
5860_1
RD
Units: kW 
System Output Pct Power L1 
Analog_Value
75
4223_1
RD
Units: % 
System Output Pct Power L2 
Analog_Value
76
4224_1
RD
Units: % 
Maximum Load Alarm Limit 
Analog_Value
77
5813_1
RW
Units: kVA 
Shutdown After Delay 
Analog_Value
78
5814_1
RW
Units: sec 
Reboot After Delay 
Analog_Value
79
5815_1
RW
Units: sec 
Output On Delay 
Analog_Value
80
5816_1
RW
Units: sec 
System Status
System Capacity 
Analog_Value
91
5821_1
RD
Units: kVA 
Frame Capacity 
Analog_Value
92
5822_1
RD
Units: kVA 
Number of Installed Power Modules 
Analog_Value
93
5823_1
RD
Number Of Active Power Modules 
Analog_Value
94
5824_1
RD
Number Of Power Modules With Warnings 
Analog_Value
95
5825_1
RD
Number Of Failed Power Modules 
Analog_Value
96
5826_1
RD
Number of Installed Battery Strings 
Analog_Value
97
5827_1
RD
Number of Active Battery Strings 
Analog_Value
98
5828_1
RD
Number of Battery Strings With Warnings 
Analog_Value
99
5829_1
RD
Number of Failed Battery Strings 
Analog_Value
100
5830_1
RD
Auto Restart Delay 
Analog_Value
101
5852_1
RW
Units: sec 
No Load Warning Current Threshold 
Analog_Value
102
5866_1
RW
Units: A AC 
No Load Warning Delay 
Analog_Value
103
5867_1
RW
Units: min 
BatteryModule 1
Battery String Voltage 
Analog_Value
114
5843_1
RD
Units: VDC 
Battery Module Temperature 
Analog_Value
115
5844_1
RD
Units: deg C 
Battery Module Temperature 
Analog_Value
10115
5844_1_deg_F
RD
Units: deg F 
Number of Discharge Cycles 
Analog_Value
116
5845_1
RD
Accumulated Discharge Time 
Analog_Value
117
5846_1
RD
Units: hr 
BatteryModule 2
Battery String Voltage 
Analog_Value
128
5843_2
RD
Units: VDC 
Battery Module Temperature 
Analog_Value
129
5844_2
RD
Units: deg C 
Battery Module Temperature 
Analog_Value
10129
5844_2_deg_F
RD
Units: deg F 
Number of Discharge Cycles 
Analog_Value
130
5845_2
RD
Accumulated Discharge Time 
Analog_Value
131
5846_2
RD 
Units: hr 
BatteryModule 80
Battery String Voltage 
Analog_Value
1220
5843_80
RD
Units: VDC 
Battery Module Temperature 
Analog_Value
1221
5844_80
RD
Units: deg C 
Battery Module Temperature 
Analog_Value
11221
5844_80_deg_F
RD
Units: deg F 
Number of Discharge Cycles 
Analog_Value
1222
5845_80
RD
Accumulated Discharge Time 
Analog_Value
1223
5846_80
RD
Units: hr 
System Configuration
System Date and Time 
Analog_Value
1234
4293_1
RW
Table 103 Liebert APS
 - 
Analog
 Data (continued)
Data Label
Object Type
Instance
Object Name
Access
Notes