310
Table 104 Liebert APS
 - Multistate Data
Data Label
Object Type
Instance Object Name Access
Notes
Protocol
Server Class
MultiState_Value
1
4553_1
RD
1 = UPS
2 = AIR
3 = PMP
4 = PDU
Bypass
Bypass Qualification Status
MultiState_Value
12
4737_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
Battery
UPS Battery Status
MultiState_Value
23
4871_1
RD
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Battery is
MultiState_Value
24
5799_1
RD
1 = fully charged
2 = charging
3 = discharging
4 = not charging
(charger off) 
Automatic Battery Test 
MultiState_Value
25
5803_1
RW
1 = disabled
2 = enabled 
Auto Battery Test Interval 
MultiState_Value
26
5805_1
RW
1 = 8 weeks
2 = 12 weeks
3 = 16 weeks
4 = 20 weeks
5 = 26 weeks 
Manual Battery Test 
MultiState_Value
27
5858_1
WO
1 = Start Test 
Output
Output Qualification Status 
MultiState_Value
38
4744_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High 
Inverter
Inverter On/Off State 
MultiState_Value
49
4746_1
RD
1 = off
2 = on 
System Set To Operate With 
MultiState_Value
50
5820_1
RW
1 = No Redundancy
2 = Redundancy 
System Status
UPS Output Source 
MultiState_Value
61
4872_1
RD
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer 
System Status 
MultiState_Value
62
4123_1
RD
1 = Normal Operation
2 = StartUp
3 = Normal with Warning
4 = Normal with Alarm
5 = Abnormal Operation 
Auto Restart 
MultiState_Value
63
5831_1
RW
1 = disabled
2 = enabled