Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
84
Inverter on Bypass
40291
1
Bit 3
Standby Fan On
40291
1
Bit 4
Loss of Emergency Power
40291
1
Bit 5
Local Alarm 1
40291
1
Bit 6
Local Alarm 2
40291
1
Bit 7
Off by Remote Shutdown
40291
1
Bit 8
Local Alarm 3
40291
1
Bit 9
Local Alarm 4
40291
1
Bit 10
Compressor 1 Run Hours
40019
1
Compressor 2 Run Hours
40020
1
Fan Motor Run Hours
40021
1
Humidifier Run Hours
40022
1
Setpoints (View)
Temperature Setpoint
40010
1
(R/W)
Temperature Tolerance
40011
1
(R/W)
Humidity Setpoint
40012
1
(R/W)
Humidity Tolerance
40013
1
(R/W)
High Temp Alarm Setpoint
40014
1
(R/W)
Low Temp Alarm Setpoint
40015
1
(R/W)
High Humd Alarm Setpoint
40016
1
(R/W)
Low Humidity Alarm Setpoint
40017
1
(R/W)
Winter Start Delay
40028
1
Minutes (R/W)
Auto Flush Rate
40029
1
% (R/W)
Chill Water Flush Rate
40030
1
Hours (R/W)
Auto Restart Delay
40031
1
0.1 minute (R/W)
Control Points (Set)
Unit On / Off
40349
1
Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint
40350
1
Temperature Tolerance
40350
1
1000
Humidity Setpoint
40351
1
Humidity Tolerance
40351
1
1000
Reheat Lockout
40349
1
Bit 2 On=RH Off; Bit 3 On=RH On
Humidifier Lockout
40349
1
Bit 4 On=HL Off; Bit 5 On=HL On
Trendable Points (Set)
Temperature
1
Humidity
1
Reports
Trend
1
Status
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 27
Liebert Challenger 3000
, Liebert Deluxe System/3
, Liebert Himod
, Liebert ICS
- Input and Holding - LAM (continued)
Controller
Advanced Microprocessor - LAM
Liebert Products
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert Himod (LNA version - Using Liebert SiteScan
®
)
Liebert ICS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units