Emerson BACNET IP Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
84
Inverter on Bypass
—
40291
1
—
Bit 3
Standby Fan On
—
40291
1
—
Bit 4
Loss of Emergency Power
—
40291
1
—
Bit 5
Local Alarm 1
—
40291
1
—
Bit 6
Local Alarm 2
—
40291
1
—
Bit 7
Off by Remote Shutdown
—
40291
1
—
Bit 8
Local Alarm 3
—
40291
1
—
Bit 9
Local Alarm 4
—
40291
1
—
Bit 10
Compressor 1 Run Hours
—
40019
1
—
—
Compressor 2 Run Hours
—
40020
1
—
—
Fan Motor Run Hours
—
40021
1
—
—
Humidifier Run Hours
—
40022
1
—
—
Setpoints (View)
Temperature Setpoint
Temperature Setpoint
—
40010
1
—
(R/W)
Temperature Tolerance
—
40011
1
—
(R/W)
Humidity Setpoint
—
40012
1
—
(R/W)
Humidity Tolerance
—
40013
1
—
(R/W)
High Temp Alarm Setpoint
—
40014
1
—
(R/W)
Low Temp Alarm Setpoint
—
40015
1
—
(R/W)
High Humd Alarm Setpoint
—
40016
1
—
(R/W)
Low Humidity Alarm Setpoint
—
40017
1
—
(R/W)
Winter Start Delay
—
40028
1
—
Minutes (R/W)
Auto Flush Rate
—
40029
1
—
% (R/W)
Chill Water Flush Rate
—
40030
1
—
Hours (R/W)
Auto Restart Delay
—
40031
1
—
0.1 minute (R/W)
Control Points (Set)
Unit On / Off
Unit On / Off
—
40349
1
—
Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint
—
40350
1
—
—
Temperature Tolerance
—
40350
1
1000
—
Humidity Setpoint
—
40351
1
—
—
Humidity Tolerance
—
40351
1
1000
—
Reheat Lockout
—
40349
1
—
Bit 2 On=RH Off; Bit 3 On=RH On
Humidifier Lockout
—
40349
1
—
Bit 4 On=HL Off; Bit 5 On=HL On
Trendable Points (Set)
Temperature
Temperature
—
—
1
—
—
Humidity
—
—
1
—
—
Reports
—
—
—
—
Trend
—
—
1
—
—
Status
—
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 27
Liebert Challenger 3000
™
, Liebert Deluxe System/3
™
, Liebert Himod
™
, Liebert ICS
™
- Input and Holding - LAM (continued)
Controller
Advanced Microprocessor - LAM
Liebert Products
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert Himod (LNA version - Using Liebert SiteScan
®
)
Liebert ICS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units