Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
85
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 28
Liebert DataMate
, Liebert Mini-Mate Plus
, Liebert Mini-Mate2
 - Input and
Holding - L0B
Controller
Small Systems - L0B
Liebert Products
Liebert DataMate
Liebert Mini-Mate Plus
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Status Points (View)
Temperature
40001
1
Humidity
40002
1
Cooling
40003
1
1=On / 0=Off
Heating
40004
1
1=On / 0=Off
Humidification
40005
1
1=On / 0=Off
Dehumidification
40006
1
1=On / 0=Off
Econ-o-Cycle
40007
1
1=On / 0=Off
Stages
40008
1
% Capacity
40009
1
Alarm Points
Communications
40289
1
Bit 0
Local Off
40289
1
Bit 1
Remote Off
40289
1
Bit 2
High Temperature
40289
1
Bit 3
Low Temperature
40289
1
Bit 4
High Humidity
40289
1
Bit 5
Low Humidity
40289
1
Bit 6
Setpoints (View)
None
1
Control Points (Set)
Unit On/Off
40011
1
1=On / 0=Off (R/W)
Remote On/Off
40349
1
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Trendable Points (Set)
Temperature
1
Humidity
1
Reports
Trend
1
Status
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.