Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Thermal Management Products
85
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 28
Liebert DataMate
™
, Liebert Mini-Mate Plus
™
, Liebert Mini-Mate2
™
- Input and
Holding - L0B
Controller
Small Systems - L0B
Liebert Products
Liebert DataMate
Liebert Mini-Mate Plus
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Status Points (View)
Temperature
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Cooling
—
40003
1
—
1=On / 0=Off
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
Dehumidification
—
40006
1
—
1=On / 0=Off
Econ-o-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Alarm Points
Communications
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Remote Off
—
40289
1
—
Bit 2
High Temperature
—
40289
1
—
Bit 3
Low Temperature
—
40289
1
—
Bit 4
High Humidity
—
40289
1
—
Bit 5
Low Humidity
—
40289
1
—
Bit 6
Setpoints (View)
None
None
—
—
1
—
—
Control Points (Set)
Unit On/Off
Unit On/Off
—
40011
1
—
1=On / 0=Off (R/W)
Remote On/Off
—
40349
1
—
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Trendable Points (Set)
Temperature
Temperature
—
—
1
—
—
Humidity
—
—
1
—
—
Reports
—
—
—
—
Trend
—
—
1
—
—
Status
—
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.