Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
89
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
EPO Shutdown
40291
1
Bit 8
Local Alarm 3
43291
1
Bit 9
Local Alarm 4
40291
1
Bit 10
Run Times (View)
Compressor 1 Run Hours
40019
1
Compressor 2 Run Hours
40020
1
Glycol Run Hours
1
Fan Motor Run Hours
40021
1
Humidifier Run Hours
40022
1
Reheat 1 Run Hours
1
Reheat 2 Run Hours
1
Reheat 3 Run Hours
1
Chilled H2O Valve Run Hours
1
Setpoints (View)
Temperature Setpoint
40010
1
(R/W)
Temperature Tolerance
40011
1
(R/W)
Humidity Setpoint
40012
1
(R/W)
Humidity Tolerance
40013
1
(R/W)
High Temperature Alarm Setpoint
40014
1
(R/W)
Low Temp Alarm Setpoint
40015
1
(R/W)
High Humidity Alarm Setpoint
40016
1
(R/W)
Low Humidity Alarm Setpoint
40017
1
(R/W)
Winter Start Delay
40028
1
Minutes (R/W)
Auto Flush Rate
40029
1
% (R/W)
Chill Water Flush Rate
40030
1
Hours (R/W)
Auto Restart Delay
40031
1
0.1 minute (R/W)
Control Points (Set)
Unit Status (On / Off)
40018
1
1=On / 0=Off (R/W)
Unit On / Off
40349
1
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint
40350
1
(W)
Temperature Tolerance
40350
1
1000
(W)
Humidity Setpoint
40351
1
-
(W)
Humidity Tolerance
40351
1
1000
(W)
Reheat Lockout
40349
1
Bit 2 On=RH Off
Bit 3 On=RH On
Humidifier Lockout
40349
1
Bit 4 On=HL Off
Bit 5 On=HL On
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 30
Liebert Mini-Mate2
 8 Ton - Input and Holding - L8T (continued)
Controller
L8T
Liebert Products
Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes 
Units