Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Thermal Management Products
89
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
EPO Shutdown
—
40291
1
—
Bit 8
Local Alarm 3
—
43291
1
—
Bit 9
Local Alarm 4
—
40291
1
—
Bit 10
Run Times (View)
Compressor 1 Run Hours
Compressor 1 Run Hours
—
40019
1
—
—
Compressor 2 Run Hours
—
40020
1
—
—
Glycol Run Hours
—
—
1
—
—
Fan Motor Run Hours
—
40021
1
—
—
Humidifier Run Hours
—
40022
1
—
—
Reheat 1 Run Hours
—
—
1
—
—
Reheat 2 Run Hours
—
—
1
—
—
Reheat 3 Run Hours
—
—
1
—
—
Chilled H2O Valve Run Hours
—
—
1
—
—
Setpoints (View)
Temperature Setpoint
Temperature Setpoint
—
40010
1
—
(R/W)
Temperature Tolerance
—
40011
1
—
(R/W)
Humidity Setpoint
—
40012
1
—
(R/W)
Humidity Tolerance
—
40013
1
—
(R/W)
High Temperature Alarm Setpoint
—
40014
1
—
(R/W)
Low Temp Alarm Setpoint
—
40015
1
—
(R/W)
High Humidity Alarm Setpoint
—
40016
1
—
(R/W)
Low Humidity Alarm Setpoint
—
40017
1
—
(R/W)
Winter Start Delay
—
40028
1
—
Minutes (R/W)
Auto Flush Rate
—
40029
1
—
% (R/W)
Chill Water Flush Rate
—
40030
1
—
Hours (R/W)
Auto Restart Delay
—
40031
1
—
0.1 minute (R/W)
Control Points (Set)
Unit Status (On / Off)
Unit Status (On / Off)
—
40018
1
—
1=On / 0=Off (R/W)
Unit On / Off
—
40349
1
—
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint
—
40350
1
—
(W)
Temperature Tolerance
—
40350
1
1000
(W)
Humidity Setpoint
—
40351
1
-
(W)
Humidity Tolerance
—
40351
1
1000
(W)
Reheat Lockout
—
40349
1
—
Bit 2 On=RH Off
Bit 3 On=RH On
Humidifier Lockout
—
40349
1
—
Bit 4 On=HL Off
Bit 5 On=HL On
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 30
Liebert Mini-Mate2
™
8 Ton - Input and Holding - L8T (continued)
Controller
L8T
Liebert Products
Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes
/
Units