Modbus 485 and Modbus IP Protocols - Thermal Management Products
87
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Setpoints (View)
Temperature —
Temperature —
40010
1
—
—
Temp Tolerance
—
40011
1
—
—
Humidity —
40012
1
—
—
Humidity Tolerance
—
40013
1
—
—
High Temperature Alarm
—
40014
1
—
—
Low Temperature Alarm
—
40015
1
—
—
High Humidity Alarm
—
40016
1
—
—
Low Humidity Alarm
—
40017
1
—
—
Chill Water Flush Rate
—
40025
1
—
Hours (R/W)
Auto Restart Delay
—
40026
1
—
0.1 minute (R/W)
Control Points (Set)
Unit On/Off
Unit On/Off
—
40018
1
—
1=On / 0=Off (R/W)
Remote On/Off
—
40349
1
—
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint
—
40350
1
—
(W)
Temperature Tolerance
—
40350
1
1000
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Humidity Setpoint
—
40351
1
-
(W)
Humidity Tolerance
—
40351
1
1000
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Trendable Points (Set)
Temperature
Temperature
—
—
1
—
—
Humidity
—
—
1
—
—
Reports
Trend
Trend
—
—
1
—
—
Status
—
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 29
Liebert DataMate
™
, Liebert Mini-Mate2
™
- Input and Holding - MM2 (continued)
Controller
MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units