Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
87
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Setpoints (View)
Temperature —
40010
1
Temp Tolerance
40011
1
Humidity —
40012
1
Humidity Tolerance
40013
1
High Temperature Alarm
40014
1
Low Temperature Alarm
40015
1
High Humidity Alarm
40016
1
Low Humidity Alarm
40017
1
Chill Water Flush Rate
40025
1
Hours (R/W)
Auto Restart Delay
40026
1
0.1 minute (R/W)
Control Points (Set)
Unit On/Off
40018
1
1=On / 0=Off (R/W)
Remote On/Off
40349
1
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint
40350
1
(W)
Temperature Tolerance
40350
1
1000
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Humidity Setpoint
40351
1
-
(W)
Humidity Tolerance
40351
1
1000
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Trendable Points (Set)
Temperature
1
Humidity
1
Reports
Trend
1
Status
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 29
Liebert DataMate
, Liebert Mini-Mate2
 - Input and Holding - MM2 (continued)
Controller
MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units