Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
203
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 72
Liebert SICE 7200
™
- Input and Holding - SSC
Controller
System Control Cabinet - SSC
Liebert Products
Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes
/
Units
Output Voltage L1-L2
—
40001
1
—
V
Output Voltage L2-L3
—
40002
1
—
V
Output Voltage L3-L1
—
40003
1
—
V
Output Amps L1
—
40004
1
—
A
Output Amps L2
—
40005
1
—
A
Output Amps L3
—
40006
1
—
A
Power L1
—
40007
1
—
kW
Power L2
—
40008
1
—
kW
Power L3
—
40009
1
—
kW
Bypass Frequency
—
40010
1
10
Hz
Battery Voltage
—
40012
1
—
V
Battery Amperage
—
40013
1
—
A
Apparent Power L1
—
40014
1
—
kVA
Apparent Power L2
—
40015
1
—
kVA
Apparent Power L3
—
40016
1
—
kVA
% Load L1
—
40017
1
—
%
% Load L2
—
40018
1
—
%
% Load L3
—
40019
1
—
%
% Battery Charge
—
40020
1
—
%
Battery Temperature
—
40021
1
—
deg C
Battery Time Remaining
—
40022
1
—
Minutes
Communications
—
40289
1
—
Bit 0
Bypass Switch Open
—
40289
1
—
Bit 1
Output Switch Open
—
40289
1
—
Bit 2
Battery CB Open
—
40289
1
—
Bit 3
Manual Bypass Closed
—
40289
1
—
Bit 4
Bypass Absent
—
40289
1
—
Bit 5
Bypass Overvoltage
—
40289
1
—
Bit 6
Bypass Undervoltage
—
40289
1
—
Bit 7
Bypass Frequency Error
—
40289
1
—
Bit 8
Bypass Ph Rotation Error
—
40289
1
—
Bit 9
Bypass SCR Failure
—
40289
1
—
Bit 10
Bypass Off
—
40290
1
—
Bit 0
Bypass Off
—
40290
1
—
Bit 1
Load On Bypass
—
40290
1
—
Bit 2
Bypass Overtemperature
—
40290
1
—
Bit 3
Inverter Non Sync
—
40290
1
—
Bit 4
Output Overvoltage
—
40290
1
—
Bit 5
Output Undervoltage
—
40290
1
—
Bit 6