Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
297
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 96
Liebert DataMate
, Liebert Mini-Mate2
 - MM2
Controller
MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Data Description
BACnet Instance
Notes
Status Points (View)
Temperature
BS01_x
Humidity
BS02_x
Cooling
BS03_x
1=On / 0=Off
Heating
BS04_x
1=On / 0=Off
Humidification
BS05_x
1=On / 0=Off
Dehumidification
BS06_x
1=On / 0=Off
Econ-o-Cycle
BS07_x
1=On / 0=Off
Stages
BS08_x
% Capacity
BS09_x
Unit On/Off
BS18_x
1=On / 0=Off
Alarm Points
Communications
BA01_x:00
Local Off
BA01_x:01
Remote Off
BA01_x:02
High Head Pressure 1
BA01_x:03
Loss of Airflow
BA01_x:05
Standby Glycol Unit On
BA01_x:06
Change Filters
BA01_x:07
High Temperature
BA01_x:08
Low Temperature
BA01_x:09
High Humidity
BA02_x:00
Low Humidity
BA02_x:01
Humidifier Problem
BA02_x:02
Smoke Detected
BA02_x:08
Loss of Water Flow
BA02_x:09
Standby Unit On
BA02_x:10
Short Cycle
BA03:01
Loss of Power
BA03:02
Local Alarm 1
BA03:06
Local Alarm 2
BA03:07
High Water
BA03:08
Local Alarm 4
BA03:09
Setpoints (View)
Temperature
BS10_x
Humidity
BS12_x
Control Points (Set)
Remote On/Off
BC01_x
Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint
BC02_x
Humidity Setpoint
BC03_x