Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
299
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
4.3
UPS Systems
Table 98
Liebert APM
, Liebert NXC
, Liebert NXR
 - Binary Data
Data Label
Object Type
Instance
Object
Name
Access
Notes
System Status
Battery Auto Test In Progress
Binary_Value
1
4172_1
RD
Active on Alarm
Battery Equalize
Binary_Value
2
4170_1
RD
Active on Alarm
Battery Charging Inhibited
Binary_Value
3
4200_1
RD
Active on Alarm
On Generator
Binary_Value
4
4315_1
RD
Active on Alarm
System Events
System Input Power Problem
Binary_Value
15
4122_1
RD
Active on Alarm
Rectifier Failure
Binary_Value
16
4295_1
RD
Active on Alarm
Inverter Failure
Binary_Value
17
4233_1
RD
Active on Alarm
Bypass Not Available
Binary_Value
18
4135_1
RD
Active on Alarm
Battery Low
Binary_Value
19
4162_1
RD
Active on Alarm
LBS Inhibited
Binary_Value
20
4758_1
RD
Active on Alarm
System Fan Failure
Binary_Value
21
4311_1
RD
Active on Alarm
Equipment Over Temperature
Binary_Value
22
4310_1
RD
Active on Alarm
System Shutdown - EPO
Binary_Value
23
4213_1
RD
Active on Alarm
Bypass Static Switch Unavailable
Binary_Value
24
4143_1
RD
Active on Alarm
Bypass - Excess Auto Retransfers
Binary_Value
25
4139_1
RD
Active on Alarm
Parallel Comm Warning
Binary_Value
26
4823_1
RD
Active on Alarm
Power Supply Failure
Binary_Value
27
4314_1
RD
Active on Alarm
Battery Over Temperature
Binary_Value
28
4219_1
RD
Active on Alarm
System Input Phs Rotation Error
Binary_Value
29
4146_1
RD
Active on Alarm
Fuse Failure
Binary_Value
30
4440_1
RD
Active on Alarm
Inverter Overload Phase A
Binary_Value
31
4234_1
RD
Active on Alarm
Inverter Overload Phase B
Binary_Value
32
4235_1
RD
Active on Alarm
Inverter Overload Phase C
Binary_Value
33
4236_1
RD
Active on Alarm
MMS Overload
Binary_Value
34
4831_1
RD
Active on Alarm
Inverter Shutdown - Overload
Binary_Value
35
4290_1
RD
Active on Alarm
System Output Fault
Binary_Value
36
4389_1
RD
Active on Alarm
Internal Communications Failure
Binary_Value
37
4300_1
RD
Active on Alarm
Battery Charging Error
Binary_Value
38
4164_1
RD
Active on Alarm
System Input Current Imbalance
Binary_Value
39
4382_1
RD
Active on Alarm
Main Battery Disconnect Open
Binary_Value
40
4173_1
RD
Active on Alarm
Inverter Static Switch SCR Short
Binary_Value
41
4391_1
RD
Active on Alarm
Battery Not Qualified
Binary_Value
42
5149_1
RD
Active on Alarm
Battery Terminals Reversed
Binary_Value
43
5150_1
RD
Active on Alarm
Battery Converter Failure
Binary_Value
44
5151_1
RD
Active on Alarm
Inverter SCR Open
Binary_Value
45
5152_1
RD
Active on Alarm
Load Sharing Fault
Binary_Value
46
5153_1
RD
Active on Alarm
DC Bus Abnormal
Binary_Value
47
5154_1
RD
Active on Alarm
Mains Input Neutral Lost
Binary_Value
48
5155_1
RD
Active on Alarm
Load Impact Transfer
Binary_Value
49
5156_1
RD
Active on Alarm
User Operation Invalid
Binary_Value
50
5157_1
RD
Active on Alarm