BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
298
Table 97
Liebert Mini-Mate2
 8 Ton - L8T
Controller
L8T
Liebert Products
Liebert Mini-Mate2 8 Ton
Data Description
BACnet Instance
Notes
Status Points (View)
Temperature
BS01_x
Humidity
BS02_x
Cooling
BS03_x
1=On / 0=Off
Heating
BS04_x
1=On / 0=Off
Humidification
BS05_x
1=On / 0=Off
De-humidification
BS06_x
1=On / 0=Off
Econ-O-Cycle
BS07_x
1=On / 0=Off
Stages
BS08_x
% Capacity
BS09_x
Unit Status (On / Off)
BS18_x
1=On / 0=Off
Alarm Points
Communications
BA01_x:00
Local Off
BA01_x:01
Remote Off
BA01_x:02
High Head Pressure 1
BA01_x:03
High Head Pressure 2
BA01_x:04
Loss of Airflow
BA01_x:05
Standby Glycol Unit On
BA01_x:06
Change Filters
BA01_x:08
High Temperature
BA01_x:09
Low Temperature
BA01_x:10
High Humidity
BA02_x00
Low Humidity
BA02_x01
Humidifier Problem
BA02_x02
Smoke Detected
BA02_x:08
Loss of Water
BA02_x:09
Standby Unit On
BA02_x:10
Short Cycle
BA03_x:01
Loss of Power
BA03_x:02
Local Alarm 1
BA03_x:06
Local Alarm 2
BA03_x:07
High Water Humidifier Pan
BA03_x:08
Setpoints (View)
Temperature Setpoint
BS10_x
Humidity Setpoint
BS12_x
Control Points (Set)
Unit On / Off
BC01_x
Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint
BC02_x
-
Temperature Tolerance
BC02_x
Multiply desired value by 1000
Humidity Setpoint
BC03_x
-
Humidity Tolerance
BC03_x
Multiply desired value by 1000
Reheat Lockout
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
BC01_x
Bit 4 on=HL off Bit 5 on=HL on