Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
311
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Auto Restart Minimum Battery Setting  MultiState_Value
64
5832_1
RW
1 = 0%
2 = 10%
3 = 20%
4 = 30%
5 = 40%
6 = 50%
7 = 60%
8 = 70%
9 = 80%
10 = 90%
PowerModule 1
Module Operating Status 
MultiState_Value
75
5833_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
Inverter Status 
MultiState_Value
76
5864_1
RD
1 = Inverter Inactive
2 = Inverter Active 
PowerModule 2
Module Operating Status 
MultiState_Value
87
5833_2
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
Inverter Status 
MultiState_Value
88
5864_2
RD
1 = Inverter Inactive
2 = Inverter Active 
PowerModule 10
Module Operating Status 
MultiState_Value
183
5833_10
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
Inverter Status 
MultiState_Value
184
5864_10
RD
1 = Inverter Inactive
2 = Inverter Active 
BatteryModule 1
Module Operating Status 
MultiState_Value
195
5834_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fau 
BatteryModule 2
Module Operating Status 
MultiState_Value
206
5834_2
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
BatteryModule 80
Module Operating Status 
MultiState_Value
1064
5834_80
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
ChargerModule
Module Operating Status 
MultiState_Value
1075
5835_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
Charger Mode 
MultiState_Value
1076
5841_1
RD
1 = Not Charging
2 = Float Charging
3 = Current Limit Charging
4 = Equalize Charging 
BypassControlModule
Module Operating Status 
MultiState_Value
1087
5836_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault 
Table 104 Liebert APS
 - Multistate Data (continued)
Data Label
Object Type
Instance Object Name Access
Notes