Emerson MODBUS IP Manuel D’Utilisation
BACnet Communications - UPS Systems
311
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Auto Restart Minimum Battery Setting MultiState_Value
64
5832_1
RW
1 = 0%
2 = 10%
3 = 20%
4 = 30%
5 = 40%
6 = 50%
7 = 60%
8 = 70%
9 = 80%
10 = 90%
PowerModule 1
Module Operating Status
MultiState_Value
75
5833_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Inverter Status
MultiState_Value
76
5864_1
RD
1 = Inverter Inactive
2 = Inverter Active
PowerModule 2
Module Operating Status
MultiState_Value
87
5833_2
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Inverter Status
MultiState_Value
88
5864_2
RD
1 = Inverter Inactive
2 = Inverter Active
PowerModule 10
Module Operating Status
MultiState_Value
183
5833_10
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Inverter Status
MultiState_Value
184
5864_10
RD
1 = Inverter Inactive
2 = Inverter Active
BatteryModule 1
Module Operating Status
MultiState_Value
195
5834_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fau
BatteryModule 2
Module Operating Status
MultiState_Value
206
5834_2
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
BatteryModule 80
Module Operating Status
MultiState_Value
1064
5834_80
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
ChargerModule
Module Operating Status
MultiState_Value
1075
5835_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Charger Mode
MultiState_Value
1076
5841_1
RD
1 = Not Charging
2 = Float Charging
3 = Current Limit Charging
4 = Equalize Charging
BypassControlModule
Module Operating Status
MultiState_Value
1087
5836_1
RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Table 104 Liebert APS
™
- Multistate Data (continued)
Data Label
Object Type
Instance Object Name Access
Notes