BACnet Communications - UPS Systems
313
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
DC Bus Current 
The current at the battery input terminals. In charging mode, the 
current will be a positive value. In discharging mode, the current will 
be a negative value 
Frame Capacity 
Total system capacity supported when the maximum number of 
power modules are installed. 
Frame Fan Fault 
The frame top outlet fan has failed. 
Inverter On/Off State 
inverter on/off state 
Inverter Shutdown - Overload 
The inverter has shutdown due to a sustained overload 
Inverter Status 
Status of the inverter output. Active means the inverter is online with 
regulated output voltage and ready to power the load. Inactive 
means the inverter is offline and not ready to power the load.
Loss of Redundancy 
The system has an insufficient number of power modules to provide 
redundancy. 
Low Battery - Shutdown Imminent 
If active and guaranteed shutdown is enabled, a low battery reserve 
condition exists that will shutdown the UPS. 
Low Battery Warning Time 
When battery time remaining falls to, or below, this value the low 
battery alarm is activated. 
Manual Battery Test 
Command to initiate a manual battery test. 
Maximum Load Alarm Limit 
Maximum load [VA] supportable without a 'Maximum Load Alarm' 
condition. 
Maximum Load Alarm 
Maximum load alarm indicating load setting has been exceeded. 
Module Operating Status 
The operating status for this Battery Module. 
Module Operating Status 
The operating status for this Bypass Control Module. 
Module Operating Status 
The operating status for this Charger Module. 
Module Operating Status 
The operating status for this Power Module. 
No Load Warning Current Threshold 
If the output current is below this number of amps for a period of [No 
Load Warning Delay] time, the [No Load Warning] will become 
active. 
No Load Warning Delay 
If the output current is below the [No Load Warning Current 
Threshold] number of amps for this period of time, the [No Load 
Warning] will become active. 
No Load Warning 
Indicates the UPS has output voltage but the output current is below 
a set threshold [No Load Warning Current Threshold] for a set period 
of time [No Load Warning Delay]. 
Number of Active Battery Strings 
The total number of active battery strings. 
Number Of Active Power Modules 
The total number of active power modules. 
Number of Battery Strings With Warnings 
The total number of battery strings with warnings. 
Number of Discharge Cycles 
The highest number of battery discharge cycles among all installed 
Battery Modules. 
Number of Discharge Cycles 
The total number of battery discharge cycles for the Battery Module 
since it was made. 
Number of EBC Installed 
The total number of Extended Battery Cabinets installed. 
Number of Failed Battery Strings 
The total number of failed battery strings. 
Number Of Failed Power Modules 
The total number of failed power modules. 
Number of Installed Battery Strings 
The total number of battery strings installed. 
Number of Installed Power Modules 
The total number of Power Modules installed. 
Number Of Power Modules With Warnings 
The total number of power modules with warnings. 
Number Of Transfers To Bypass 
The total number of transfers to bypass from inverter since system 
startup. 
Table 105 Liebert APS
 - Glossary (continued)
Data Label
Data Description