Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
312
Table 105 Liebert APS
 - Glossary
Data Label
Data Description
Accumulated Discharge Time 
The highest accumulated battery discharge time among installed 
battery modules. 
Accumulated Discharge Time 
Total accumulated discharge time for the Battery Module since it was 
made. 
Auto Battery Test Interval 
The time between automatic battery tests. 
Auto Restart Delay 
If 'Auto Restart' is set to 'enabled' the UPS will not restart the load 
after a battery discharge until this amount of time has elapsed since 
the restoration of utility power. 
Auto Restart Minimum Battery Setting 
The percent state of charge that the batteries must have before the 
unit is allowed to auto restart. 
Auto Restart 
When 'enabled', the UPS will automatically restart the load when 
utility power is restored after a battery discharge. 
Automatic Battery Test 
Enable/disable the automatic battery test schedule. 
Battery Auto Test In Progress 
Automatic battery test is in progress 
Battery Discharging 
The battery is discharging 
Battery is
Battery charge status. 
Battery Manual Test In Progress 
Manual battery test is in progress 
Battery Module Fault 
One or more battery modules are reporting a fault condition. 
Battery Module Over Temperature 
The Battery Module has detected an over temperature condition. 
Battery Module Temperature Sensor Fault 
A Battery Module temperature sensor fault has been detected. 
Battery Module Temperature 
The battery temperature measured by the Battery Module. 
Battery Module Warning 
One or more battery modules are reporting a warning condition. 
Battery Over Temperature 
A battery temperature sensor is reporting a value above a threshold 
Battery Percentage Charge 
The percentage of battery charge 
Battery String Voltage 
The voltage between the positive and negative battery terminals of a 
battery string. 
Battery Temperature Imbalance 
Excessive temperature differences between battery sensors 
detected 
Battery Temperature 
The highest battery temperature among all installed Battery Modules. 
Battery Test Failed 
Battery test failed 
Battery Test Passed 
Battery test passed 
Battery Time Remaining 
The calculated available time on battery 
Battery Volts for Cabinet 
The voltage between the positive and negative battery terminals of a 
battery cabinet 
Bypass Auto Retransfer Failed 
After performing a recoverable transfer to bypass, an attempt to auto 
retransfer from bypass to inverter failed 
Bypass Frequency Error 
The bypass frequency is outside the inverter synchronization limits 
Bypass Input Frequency 
The bypass input frequency 
Bypass Input Voltage RMS L1-L2 
The bypass input RMS voltage between Lines 1 and 2 
Bypass Input Voltage RMS L1-N 
The bypass input RMS voltage between Line 1 and Neutral 
Bypass Input Voltage RMS L2-N 
The bypass input RMS voltage between Line 2 and Neutral 
Bypass Not Available 
A problem associated with the bypass has been detected 
Bypass Overload 
Bypass overloaded, reduce load immediately. 
Bypass Qualification Status 
bypass qualification status 
Charger Mode 
The Charger Module is operating in the stated charging mode. 
Charger Module Fan Fault 
The Charger Module has detected a fan fault. 
Check Air Filter 
Please check air filter, it may need to be cleaned or replaced.