BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
314
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Off Pending
Output off pending - shutdown imminent.
Output On Delay
When a value is written to this point the output will be turned on after
the specified time has elapsed.
Output Overload
An overload exists on the output.
Output Qualification Status
output qualification status
Power Module Failure
One or more conditions indicate a power module failure, service is
required.
Power Module Fan Fault
The Power Module has detected a fan fault.
Power Module Over Temperature
The Power Module has detected an over temperature condition.
Power Module Shutdown - Over Temperature
Power Module has shutdown due to over temperature.
Power Module Warning
One or more power modules is reporting a warning condition.
Reboot After Delay
When a value is written to this point the output will be turned off after
the specified time has elapsed and then turned back on 10-30
seconds later.
Rectifier Failure
Rectifier failure - rectifier is off
Replace Battery Module
The Battery Module needs to be replaced.
Server Class
The general classification for this system
Shutdown After Delay
When a value is written to this point the system will shutdown after
the specified time has elapsed and output will remain off.
System Capacity
System capacity supported by the installed power modules.
System Date and Time
The system date and time
System Input Black Out Count
The number of occurrences, since the last reset, where the input was
not qualified to provide power to the system
System Input Brown Out Count
The number of occurrences, since the last reset, where the system
input voltage has fallen below a pre-determined threshold for a
specified amount of time
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Frequency
The system input frequency
System Input Power Factor L1
The system input power factor for Line 1
System Input Power Factor L2
The system input power factor for Line 2
System Input Power Factor L3
The system input power factor for Line 3
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS Current L1
The system input RMS current for Line 1
System Input RMS Current L2
The system input RMS current for Line 2
System Input RMS Current L3
The system input RMS current for Line 3
System Input RMS L1-L2
The System Input RMS Voltage between Line 1 and Line 2
System Input RMS L1-N
The System Input RMS Voltage between Line 1 and Neutral
System Input RMS L2-L3
The System Input RMS Voltage between Line 2 and Line 3
System Input RMS L2-N
The System Input RMS Voltage between Line 2 and Neutral
System Input RMS L3-L1
The System Input RMS Voltage between Line 3 and Line 1
System Input RMS L3-N
The System Input RMS Voltage between Line 3 and Neutral
System Output Apparent Power L1
System output apparent power on Line 1
System Output Apparent Power L2
System output apparent power on Line 2
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Frequency
The system output frequency
Table 105 Liebert APS
™
- Glossary (continued)
Data Label
Data Description