BACnet Communications - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
314
Output Load on Maint. Bypass 
The output power is supplied by the maintenance bypass 
Output Off Pending 
Output off pending - shutdown imminent. 
Output On Delay 
When a value is written to this point the output will be turned on after 
the specified time has elapsed. 
Output Overload 
An overload exists on the output. 
Output Qualification Status 
output qualification status 
Power Module Failure 
One or more conditions indicate a power module failure, service is 
required. 
Power Module Fan Fault 
The Power Module has detected a fan fault. 
Power Module Over Temperature 
The Power Module has detected an over temperature condition. 
Power Module Shutdown - Over Temperature
Power Module has shutdown due to over temperature. 
Power Module Warning 
One or more power modules is reporting a warning condition. 
Reboot After Delay 
When a value is written to this point the output will be turned off after 
the specified time has elapsed and then turned back on 10-30 
seconds later. 
Rectifier Failure 
Rectifier failure - rectifier is off 
Replace Battery Module 
The Battery Module needs to be replaced. 
Server Class 
The general classification for this system 
Shutdown After Delay 
When a value is written to this point the system will shutdown after 
the specified time has elapsed and output will remain off. 
System Capacity 
System capacity supported by the installed power modules. 
System Date and Time 
The system date and time 
System Input Black Out Count 
The number of occurrences, since the last reset, where the input was 
not qualified to provide power to the system 
System Input Brown Out Count 
The number of occurrences, since the last reset, where the system 
input voltage has fallen below a pre-determined threshold for a 
specified amount of time 
System Input Current Imbalance 
System Input Currents are Imbalanced 
System Input Frequency 
The system input frequency 
System Input Power Factor L1 
The system input power factor for Line 1 
System Input Power Factor L2 
The system input power factor for Line 2 
System Input Power Factor L3 
The system input power factor for Line 3 
System Input Power Problem 
The input is not qualified to provide power to the system 
System Input RMS Current L1 
The system input RMS current for Line 1 
System Input RMS Current L2 
The system input RMS current for Line 2 
System Input RMS Current L3 
The system input RMS current for Line 3 
System Input RMS L1-L2 
The System Input RMS Voltage between Line 1 and Line 2 
System Input RMS L1-N 
The System Input RMS Voltage between Line 1 and Neutral 
System Input RMS L2-L3 
The System Input RMS Voltage between Line 2 and Line 3 
System Input RMS L2-N 
The System Input RMS Voltage between Line 2 and Neutral 
System Input RMS L3-L1 
The System Input RMS Voltage between Line 3 and Line 1 
System Input RMS L3-N 
The System Input RMS Voltage between Line 3 and Neutral 
System Output Apparent Power L1 
System output apparent power on Line 1 
System Output Apparent Power L2 
System output apparent power on Line 2 
System Output Apparent Power 
The sum total apparent power of all system output phases 
System Output Frequency 
The system output frequency 
Table 105 Liebert APS
 - Glossary (continued)
Data Label
Data Description