Emerson 240V Manuel D’Utilisation

Page de 44
Installation
15
2.3.3 REPO Connection
The Nfinity is equipped with a Remote Emergency Power Off (REPO) connection.
Figure 2
REPO switch connections
NOTE
A jumper is factory installed between pins 1 & 2 to disable the Control Switch (SW2). 
This will prevent the unit from being started during installation. This jumper must 
be removed in order to start the unit.
!
CAUTION
To maintain safety, Signal Edge Low Voltage (SELV) barriers, and electromagnetic 
compatibility, signal cables should be segregated and run separately from power cables.
NOTE
Remove jumper before wiring.
If the installation does not 
require connection to a REPO 
system, the jumper must be 
removed.
1
2
3
4
Key to REPO switch connections
1.
24 V DC, 50mA
2.
Sense
3.
Sense
4.
Ground
REPO connections
for normally open 
switch system
REPO jumper 
connected
as shipped
REPO connections 
for normally closed 
switch system (fail-safe)
Hanger for cable-tie 
to strain relief REPO 
wiring
REPO switch 
on rear of unit
1
2
3
4
1
2
3
4