Emerson 240V Manuel D’Utilisation

Page de 44
Installation
14
OUTPUT CABLING
UPS Output Terminal Block (TB3)
Connection to External Panel Boards
208 VAC
If connected equipment operates at 208VAC only, use a single-phase panel board connected to the UPS as follows.
208 VAC and 120 VAC
If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel board connected to 
the UPS as follows.
240VAC and/or 120VAC
If connected equipment operates at 240VAC only or 120VAC only or is a combination of both, use a single-phase 
panel board connected to the UPS as follows.
1
2
3
4
5
Setup 1 - 208 VAC
208
Grounding Electrode Conductor
(Field connection must be made)
L
L
GEC
Max output current = 96A
 Connected Equipment 
Ground
 Connected Equipment 
Ground
208
UPS Output TB3
Panel Board Input
Grounding Electrode Conductor
(Field connection must be made)
1
2
3
4
5
L
L
GEC
G
1
2
3
4
5
Setup 2 - 120 VAC
120
N
208 VAC also 
available
as shown
connected
in Setup 1
Grounding Electrode Conductor
(Field connection must be made)
Max output current = 83A 
each 120 VAC circuit
L
L
GEC
120
 Connected Equipment 
Ground
Note: L2 to N 
is 88 VAC
CAUTION:
 It is important for the installing 
electrician to clearly identify the connections for 
future reference. Refer to NEC 215-8 and 210-4(d).
208
120
UPS Output TB3
Panel Board Input
120
1
2
3
4
5
L2
GEC
N
L1
L3
Grounding Electrode Conductor
(Field connection must be made)
G
1
2
3
4
5
Setup 3 - 240 VAC
240
120 VAC also
available as shown
connected in Setup 2
Grounding Electrode Conductor
(Field connection must be made)
Max output current = 83A
L
L
GEC
 Connected Equipment 
Ground
240
120
120
UPS Output TB3
Panel Board Input
1
2
3
4
5
GEC
N
L
L
Grounding Electrode Conductor
(Field connection must be made)
G