Emerson 240V Manuel D’Utilisation

Page de 44
Installation
16
2.4
Communications
2.4.1 COM Ports
Nfinity is able to communicate through multiple communication 
ports simultaneously. Use only Liebert-provided communication 
cards. Connect only Signal Edge Low Voltage (SELV)/Class 2 cir-
cuits when connecting to any communication port. 
There are two DB-9 COM ports available on the rear of the Nfinity.
COM1 - Relay Contacts
Relay contacts are available through a DB-9F communications connector. Contact closure provides 
the following: 
These contacts are rated 48 VDC, 1 amp maximum and are compatible with Liebert MultiLink™ 
software.
COM2 - Serial
Nfinity is able to communicate via Liebert proprietary protocol. This communication port can be used 
for serial communication with Liebert MultiLink software. For more detailed information, please see 
the MultiLink software documentation on the CD shipped with the Nfinity. The pin-out configuration 
of the DB-9 connector is: 
2.4.2 Intellislot™ Ports
The following communication cards may be used with Nfinity:
• Intellislot OpenComms Web Card—allows 
the Nfinity to communicate intelligently with 
your Ethernet network. The OpenComms Web 
Card must be installed in port 1.
• Intellislot MultiPort4 cards—allows up to 
four client computer systems to monitor the sta-
tus of Nfinity simultaneously.
• Intellislot Relay Contacts cards—provides 
contact closures for remote monitoring of alarm 
conditions; On Battery, On Bypass, Low Battery, 
Summary Alarm, UPS Fault and On UPS 
signals.
Pin
Assignment
1
Low Battery (normally open)
4
UPS shutdown in battery mode
(5-12 V DC for 1.5 sec)
5
Common
7
Low Battery (common)
8
On Battery (common)
9
On Battery (normally open)
Pin
Assignment
2
Transmit Data
3
Receive Data
5
Common
5
4
3
2
1
6
7
8
9
Pin Assignment
Port 1
Port 2
Port 3
Port 4
COM 1
COM 2