Emerson 40-200KVA Mode D'Emploi

Page de 132
Specifications and Technical Data
111
13.2 Cable Lengths: Floor to Connection Point Inside UPS
To help calculate the total cable length required, refer to Table 36 for the distance from the floor to 
selected connection points inside the Liebert
®
 NX
. Determine the cable length required to reach the 
Liebert NX, then add the appropriate length from the table and adequate slack for repair and 
maintenance.
Table 36
Distance to connection points on the Liebert NX UPS
Connection Point on UPS
Distance
From Floor
in. (mm)
From Top of Unit
in. (mm)
Bypass AC input supply
13 (330)
66 (1676)
UPS output AC
13 (330)
66 (1676)
Battery power
13 (330)
66 (1676)
Auxiliary cables: Monitor board (U2)
67 (1702)
11 (279)
Liebert IntelliSlot Communications
60 (1524)
19 (483)
Ground
13 (330)
66 (1676)
Parallel Board
70 (1780)
11 (279)
Table 37
Parallel system current table
System
Size
Type
kVA 
System I/P
Voltage
(VAC)
System Max
Input Current
System
Input OCPCB
Size (A)
O/P Voltage
(VAC)
Nominal
O/P Current
Rating (A)
Output
OCPCB
Size (A)
1+1
E
80
480V
135.0
200
480V
96.2
125
120
480V
202.5
300
480V
144.3
200
E1
80
480V
135.0
200
480V
96.2
125
120
480V
202.5
300
480V
144.3
200
E2
80
N/A
N/A
N/A
480V
96.2
125
120
N/A
N/A
N/A
480V
144.3
200
2+1
E
80
480V
270.0
350
480V
192.5
250
120
480V
405.0
600
480V
288.7
400
E1
80
480V
270.0
350
480V
192.5
250
120
480V
405.0
600
480V
288.7
400
E2
80
N/A
N/A
N/A
480V
192.5
250
120
N/A
N/A
N/A
480V
288.7
400
3+1
E
80
480V
405.0
600
480V
288.7
400
120
480V
607.5
800
480V
433.0
600
E1
80
480V
405.0
600
480V
288.7
400
120
480V
607.5
800
480V
433.0
600
E2
80
N/A
N/A
N/A
480V
288.7
400
120
N/A
N/A
N/A
480V
433.0
600
Type E: BB0, FB0 and KB0 configurations
Type E1: CB1, GB1, LB1 configurations;
Type E2: CB2, CB3, CB4 configurations
Use wiring rated at 75°C or greater.