Emerson 40-200KVA Mode D'Emploi

Page de 132
Specifications and Technical Data
112
13.3 Cable size and tightening torques
Table 38
External cabinet dimensions, including side panels
Wide Parallel Cabinet
 
Unit
 
Width
 
Depth
 
Height
 
mm (inch)
1240 (48.8)
965 (38)
2000 (78.7)
Narrow Parallel Cabinet
 
Unit
 
Width
 
Depth
 
Height
 
mm (inch)
845 (33.2)
965 (38)
2000 (78.7)
33 in. Battery Cabinet
 
Unit
 
Width
 
Depth
 
Height
 
mm (inch)
845 (33.2)
965 (38)
2000 (78.7)
Table 39
Cable size tightening torque at Liebert
®
 NX
 40kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
4
10  N-m
Main Input
(Dual Input)
4
10  N-m
Bypass Input
(Dual Input)
4
10  N-m
Output
3
10 N-m
Table 40
Cable size tightening torque at Liebert NX 60kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
1
10  N-m
Main Input
(Dual Input)
1
10  N-m
Bypass Input
(Dual Input)
2
10  N-m
Output
2
10 N-m
Table 41
Cable size tightening torque at Liebert NX 80kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
2/0
10 N-m
Main Input
(Dual Input)
2/0
10 N-m
Bypass Input
(Dual Input)
1/0
10 N-m
Output
1/0
10 N-m