Emerson 40-200KVA Mode D'Emploi

Page de 132
Specifications and Technical Data
113
Table 42
Cable size tightening torque at Liebert
®
 NX
 100kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
4/0
10 N-m
Main Input
(Dual Input)
4/0
10 N-m
Bypass Input
(Dual Input)
2/0
10 N-m
Output
2/0
10 N-m
Table 43
Cable size tightening torque at Liebert NX 120kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
250
10 N-m
Main Input
(Dual Input)
250
10 N-m
Bypass Input
(Dual Input)
4/0
10 N-m
Output
4/0
10 N-m
Table 44
Cable size tightening torque at Liebert NX 160kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
2-3/0
26 N-m
Main Input
(Dual Input)
2-3/0
26 N-m
Bypass Input
(Dual Input)
2-3/0
26 N-m
Output
2-3/0
26 N-m
Table 45
Cable size tightening torque at Liebert NX 200kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
2-4/0
26 N-m
Main Input
(Dual Input)
2-4/0
26 N-m
Bypass Input
(Dual Input)
2-4/0
26 N-m
Output
2-4/0
26 N-m
Table 46
Cable size tightening torque at Liebert NX 480V Battery Cabinet DC input bus terminals
Cabinet
Rating
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus and Lug Body
225A
4/0AWG
15 N-m
350A
400kcmil
15 N-m
600A
2-350kcmil
26 N-m
All control wiring and power wiring must be 600V rated wire.