Toshiba tic-lf414c Manuel D’Utilisation

Page de 16
TIC-LF414C 
3
 
Digital input DI (opt.) 
Signal type:  20 to 30Vdc voltage signal 
Input resistance: 2.7k
Ω 
Number of inputs: one point 
DI function — One of the following functions can be 
assigned to the optional DI signal. 
Range switching — Selects either the higher or 
lower range in the unidirectional or bidirectional 
2-range setting. 
Totalizer control — Starts and stops the built-in 
totalizer. 
Fixed-value outputs —Outputs fixed-values for 
current and pulse outputs. 
Zero adjustment — Executes zero adjustment 
(on-stream at zero flow rate). 
Output signals 
Current output: 
4–20mAdc (load resistance 0 to 750
Ω) 
Note: The current output cannot be used with the 
PROFIBUS-PA communication. 
Digital outputs — One point (std.) and one more 
point is optionally available as follows. 
Digital output DO1 (std.): 
Output type: Transistor open collector 
Number of outputs: One point 
Output capacity: 30Vdc, 200mA maximum 
Digital output DO2 (opt.): 
Output type:  
Solid-state relay output (non polarity) 
Number of outputs: One point 
Output capacity: 150Vdc, 150mA maximum  
or 150Vac (peak to peak), 100mA maximum 
DO1 and DO2 functions — One of the following 
functions can be assigned to DO1 (std.) and/or 
DO2 (opt.) 
• Pulse output (available only for DO1, DO2) 
Pulse rate: 3.6 to 36,000,000 pulses/hr (DO1) 
3.6 to 360,000 pulses/hr (DO2) 
(Over 3,600,000 pulses/hr, auto-setting) 
Pulse width: 0.5 to 500ms (but less than half of 
the period for 100% flow rate) 
Note: The same and simultaneous  pulse is not 
available between DO1 and DO2.) 
• Multi-range selection outputs (Note 1) 
• High, High high, Low, and/or Low low alarm 
outputs (Note 2) 
• Empty pipe alarm output 
• Digital Output Active Status (DO1 and DO2) 
(Note 2) 
• Preset count output 
• Converter failure alarm output 
Note 1: Two outputs (DO1 and DO2) are needed for 
4-range switching and forward/reverse 2-range 
switching. 
Note 2:  Normal Open (default set) or Normal Close is 
selected for alarm outputs when programming. 
When power failure occurs, unit will be fault to 
Normal Open. 
Communications output:  
• HART (std.) — Digital signal is superimposed on 
4–20mAdc current signal as follows: 
Conforms to HART protocol 
Load resistance: 240 to 750
Ω 
Load capacitance: 0.25µF maximum 
Load inductance: 4mH maximum 
• PROFIBUS (opt.) 
Protocol: PROFIBUS-PA 
Baud rate: 31.25kbps 
Bus voltage: 9-30VDC 
Consumption electric current of bus: less than 16mA 
Manufacture Ident-No.: 093B
HEX 
Standard Ident-No.: 9740
HEX
 
Slave address: 0-126 (Default address is 126) 
Profile: Profile Ver.3.01 for Process Control 
Devices 
Function blocks: AI(Flow)×1 , Totalizer×1 
LCD display: 
Full dot-matrix 128×128 dot LCD display 
(back–light provided) 
The data on the LCD inside the converter can rotate 
to 90, 180, and 270 degrees by a software, without 
rotating the indicator itself. (Combined type only) 
Parameter settings — Parameters can be set as 
follows: 
• IR Switches: Three key switches are provided to 
set configuration parameters.  
• Digital communication: The AF900 hand-held 
 terminal or PROFIBUS   is needed to set 
parameters. 
• Zero adjustment: Zero point adjustment can be 
started by pressing the switch in the converter. 
• Damping: 0.5 to 60 seconds (selectable in one 
second increments) 
“Field re-verification” 
Mag-Prover
 – Toshiba’s 
Zero span calibration tool allows unit to be 
re-calibrated and verified using an internal 
software program (For more information contact 
Toshiba International Corp.)