Schneider Electric MGE Galaxy 5000 Manuel D’Utilisation

Page de 17
160/320/520kVA depending on model selected.  Secondary UPS isolation breakers (2 to 6) are 
standard – must be determined pre-orderd.  Includes: PM800 Meter for SBC System Level 
Metering. 
 
E.  42” Distribution Cabinet:  Distribution Cabinets are an available option to the System Bypass 
Cabinets not individual UPS module.  Available in 4 or 8 breaker combinations (225A only). 
 
F.  Remote Alarm Status Panel A wall mounted panel, 17.5”Hx12”Wx4”D, with eight (8) 
indicating LED's shall display UPS status and any active alarms. The alarms shall be a 
latching type, such that if an alarm is triggered, the LED will stay ON (latch) even if the alarm 
is corrected.  This feature will provide the operator the chance to verify the occurrence of the 
alarm.  
 
Choose either:   2 Module, 3 Module, 4 Module, 5 Module, or 6 Module RASP model. 
 
G. Seismic 
Anchors:  Seismic Zone 4 anchors shall be available for all system cabinets.  
 
H. Dual 
Input:   Provided to accommodate a separate input source. 
 
M.  Bypass Input Fuses:  Bypass input fuses are optionally provided on the bypass for current 
limiting of 65kAIC. 
 
N.  Top Entry Cabinet:  16” cabinet allows top power cable entry to UPS unit. 
 
 
 
5.0 
FIELD QUAILTY CONTROL & SERVICE ORGANIZATION 
 
5.1 
FIELD SERVICE ENGINEER QUALIFICATIONS 
 
The manufacturer must employ a 7 X 24 nationwide (international where applicable) field service 
organization with rapid access to all regions of the nation. The responding service professionals 
must be factory-trained engineers with an accredited and proven competence to service three 
phase UPS. 
 
5.2 SPARE 
PARTS 
 
Field Engineers must have immediate access to recommended spare parts with additional parts 
storage located in regional depots. Additional spare parts shall be accessible on a 7 x 24 basis 
from the national depot and must be expedited on a next available flight basis or via direct courier 
(whichever mode is quickest).  
 
 
5.3 
MAINTENANCE TRAINING  
 
The manufacturer shall make available to the customer various levels of training ranging from 
basic UPS operation to UPS maintenance.  
 
5.4 
MAINTENANCE & SERVICE CONTRACTS 
 
The manufacturer shall offer additional preventative maintenance and service contracts covering 
both the UPS and the battery bank. Accredited professional service engineers employed 
exclusively in the field of critical power systems service shall perform all maintenance and 
service. The manufacturer shall also offer extended warranty contracts.  
 
 
APC – MGE Galaxy 5000 Specification  (60Hz) 
13
 
Effective:  June 1, 2008 REV X0 JJG 
Parallel Module