Temco DV1000/1200/1400 Series
76657
Troubleshooting
SIT Millivolt Valve
NOTE: Before troubleshooting the gas control system, be sure external shut off is in the “ON” position.
WARNING: Before doing any gas control service work, remove glass front!
  Table 1
   
Valve Type 
 
Main Operator 
 
Safety Magnet
   
NOVA MV Plus 
Minimum Voltage  145mV 
Hold-in Current 
Less than 285mA
   
 
Coil Resistance 
2.25Ω ± 0.5Ω 
Drop-out Current 
Greater than 125mA
   
 
 
 
Coil Resistance 
0.108Ω ± 0.003Ω
  Problem 
Possible Cause 
Solution
  Pilot will not light. 
Air in gas lines. 
Bleed all air from gas lines.
   
Wrong inlet pressure. 
With the main burner functioning, adjust the inlet  
   
 
pressure regulator to supply gas to the appliance  
   
 
within the design parameters of the appliance manu- 
   
 
facturer.  (Typically 7”NG, 11”LPG).
   
Defective spark electrode. 
Replace piezo wire if insulation is cracked or the tip  
   
 
is corroded. 
 
 
 
 
 
   
 
Verify that the spark gap between the pilot and the  
   
 
electrode is correct.
   
Defective piezo wire. 
Replace piezo wire if insulation is damaged, or the  
   
 
wire is broken or corroded.
   
Safety interlock function  
Allow thermocouple to cool until the mv drops below  
   
engaged. 
the hold-in requirements of the safety magnet, (30  
   
 
seconds or less).  Re-light pilot.
  Pilot will not hold. 
Wrong inlet pressure.  
With the main burner functioning, adjust   the inlet  
   
 
pressure regulator to supply gas to the appliance 
   
 
within design parameters of the appliance manufac 
   
 
turer. (Typically 7”NG, 11”LPG)
   
Pilot adjustment screw not  
After the pilot has been lit for approximately three  
   
properly adjusted. 
minutes, and only the thermo-generator wire con- 
   
 
nected to the main operator head, measure the volt- 
   
 
age across TPTH and TP.  This open circuit volt   
   
 
age should be between 500mv and 750mv. Tune  
   
 
the pilot adjustment screw until the mv reading    
   
 
falls within these parameters. (Counter-clockwise  
   
 
increases mv reading, clockwise decreases).
   
Thermocouple or  
Make certain that the thermocouple and thermo-  
   
thermo-generator not 
generator are fully inserted and tightened into their 
   
properly inserted into the pilot 
receptacles in the pilot head. The thermocouple   
   
housing 
should be threaded into the valve hand-tight, plus  
   
 
1/4 turn with wrench.
   
Thermocouple or  
With the thermocouple and thermo-generator tips  
   
thermo-generator has film  
cool, clean the upper 3/8” with a very fine emery   
   
build-up on tip. 
cloth.
   
Electrical resistance too high. 
Using a very fine emery cloth, clean thermo-genera- 
   
 
tor and  thermocouple connections at valve. Tighten  
   
 
thermocouple into valve hand-tight, plus 1/4 turn  
   
 
with a wrench.
System Checks