Innovative Control Systems Inc IGWT-660098 Manuel D’Utilisation

Page de 156
15-2 System Maintenance & Testing                                                                                LC 1200 Manual   
Zone, Lock Test 
When a Tag approaches a monitored door zone 
equipped with Locks, the Lock should engage. 
When the Tag leaves the monitored zone, the 
Lock should disengage. This test will evaluate 
this operation. 
Note: In the event of a fire, all Locks are 
disabled and the door can be opened 
immediately. 
Test results should be written down and kept in a 
test log.  Make your own, or use the included, to 
ensure that every monitored zone is tested.  
These test reports should become part of your 
permanent quality assurance records.   
1.  Notify staff and security that you will be 
testing zone performance and alarms 
may be generated. They should pay 
special attention to traffic during this 
time. 
2.  While not in a monitored zone, use a 
TAD to activate the test Tag. 
3.  Hold the test Tag in your hand and 
approach each monitored door zone.   
4.  Each door should lock as you approach. 
NOTE: 
You may be able to hear the lock 
“click” as it changes states. Otherwise,
 
For 3000 Series Magnetic Locks, you 
can push on the door to verify the Lock 
is engaged. For 3101 Series Magnetic 
Locks, the LED will turn from green to 
red when the Lock is engaged. 
However, do not open the door; this test 
is intended only for verifying that a door 
locks when a Tag approaches.  
5.  As you approach each zone, try varying 
your approach angle (i.e., straight on, 
from the sides, down low, etc.). Make 
sure there is adequate coverage from all 
angles leading to the monitored zone.  
6.  Record the results (pass or fail).  
7.  If the test fails to lock the door: 
a.  Notify staff and security of the 
vulnerable area. 
b.  Check for visible damage or 
tampering to the zone equipment. 
c.  Have a maintenance technician 
verify power to the zone equipment.  
d.  Have a maintenance technician 
verify the FPI is set properly. 
e.  Call your Accutech Representative. 
8.  To reset the Lock, deactivate the test 
Tag or leave the monitored zone. 
Depending upon your settings, the Lock 
may disengage itself automatically. 
Otherwise enter a Keypad Reset code.