Eaton PPF3003CEI Manuel D’Utilisation

Page de 4
   
 
www.eaton.com/powerquality     www.eatonelectric.com.au
Eaton® PPFi
 
Class II/Cat C & D, 3 Phase Premium Power Filter
Series Power & Noise Filter with Shunt Surge Diverter  
3 Phase, 100-400A, 80-240kA
 Applications:
•  All Power Circuits including "Point-of-Entry"
•  Telecommunications Systems & Rectifiers
•  Process & Control Systems & UPS Systems
•  Computer Systems & Medical Systems
•  AV circuits for clubs & hotels
•  All sensitive Electronic Equipment
  Key Features:
•  Surge suppression & filtering in a single package
•  Standard Current ratings from 100A to 400A
•  1 mode, Multi-Element Series Filter
•  2 mode, 3 stage Surge Diverter
•  Surge suppression ratings from 80kA to 240kA
•  Provides extensive high frequency & RF filtering
•  Incorporates a EN certified EMI/RFI filter
•  Panel-mounted mimic display
•  Protection Fail Alarm Relay
•  Enclosed in IP24 painted steel cabinet
•  5 Year Warranty
  Options:
•  Custom configurations
•   Isolation switches & circuit breakers
•  Custom cabinets
•  Chassis Mount versions
The PPFI is designed to provide point-of-entry (Category 
C) & sub-circuit protection (Category B) against power 
surges caused by external sources such as lightning strikes 
& substation switching as well as providing a measure of 
protection from surge events generated on the secondary side 
of the filter.  An ideal device for all Category locations.
The PPFI is a 3-stage protection system utilising primary & 
secondary MOV protection in conjunction with a Low-Q LC 
filter. The unit  provides filtering of the line harmonics, noise 
& RF transmitters with a cut-off frequency of <10kHz & a 
minimum attenuation of 70dB above 1MHz. Special care has 
been taken in the design of the filter to minimise ringing caused 
by light loads, surge diverter operation & inductive load back-
EMF. 
All models in the PPFI Series are fully enclosed in wall 
mounting IP24 steel enclosures.  A graphical mimic display 
provides at-a-glance indication of the status of the PPFI with 
indicators showing correct functions in green & faults in 
red. The alarm function provides a summary alarm output for 
protection failure & power failure.