Beha Amprobe GT-800 PRO KITVDE-tester 4472081 Manuel D’Utilisation

Codes de produits
4472081
Page de 76
GT-600/GT-800 Instruction Manual 
17 
 
 
  The tests should only be performed by competent persons who are familiar 
with the requirements of the type of tests suitable for portable appliances. 
  It is potentially hazardous for both user and appliance should the wrong type 
of tests be undertaken or if testing is carried out in an incorrect sequence. 
  It is important that you fully understand the various tests required and how 
they should be performed. 
  The appliance must have passed the visual inspection, the protective bonding 
resistance test (class I), and the insulation test (in this sequence) prior to any 
other test. If any of these fail further testing must be stopped and any faults 
must be rectified. 
  During the protective conductor current test, the touch current test and the 
load test, the appliance will be energized at mains voltage. For this purpose, 
switch on the appliance. Appliances driven by motors or equipped with 
heating units may present a danger for the person testing (comply with the 
appliance instruction manual!). Please ensure that the appliance is in a safe 
condition to run and secure prior to testing. 
 
 
Visual Inspection
 
 
Visually inspect the appliance before starting electrical tests. 
 
Check the appliance for the following: 
 
  Condition of the appliance cables, i.e. no cuts, cracks or any physical damage 
to the outer insulation layer. 
  Condition of the plug, cable securely attached, no signs of overheating and 
that fitted fuses are correctly rated. 
  Any signs of damage, and that any mains or control switches will physically 
switch on and off. 
  Any sockets for sign of overheating or physical damage.