Beha Amprobe GT-800 STD KITVDE-tester 4472062 Manuel D’Utilisation

Codes de produits
4472062
Page de 76
GT-600/GT-800 Instruction Manual 
42 
 
 
AUTO Test (GT-800 only) 
 
This is most common used test mode as it leads the operator through the whole 
test procedure. There are 13 factory-programmed Auto-Tests and free space for 
additional 17 customer-created ones. 
 
Factory-programmed Auto-Tests for class I appliances (GERMAN REGION) 
(listed figures are limit values in each test) 
 
Tests 
145 146 147 148 149 150 151 160 161 
Visual 
Inspection 
Yes Yes Yes Yes Yes Yes Yes Yes Yes 
Protective bonding 
resistance 200 mA (
) 
0.30
0.30
0.30
0.30
- - - - 
Protective bonding 
resistance 5 A (
) 
- 0.3 -  -  - 0.3 
1.00 -  - 
Insulation resistance 500 V 
(M
) 
1.00
1.00
0.30
-  1.00 1.00 1.00
1.00
Substitute leakage current 
(mA) 
-  - 3.50
-  - 3.50 
3.50 -  - 
Protective conductor 
current (mA) 
3.50
3.50
- 3.50
3.50
-  - 3.50
3.50
Touch 
current 
(mA) 
- - - - 0.50
- - - 0.50
Apparent 
power 
(kVA)  3.7 
3.7 
- 3.7 
3.7 
- - 3.7 
3.7 
 
Factory-programmed Auto-Tests for class II appliances (GERMAN REGION) 
(listed figures are limit values in each test) 
 
Tests 
241 242 243 244 
Visual 
Inspection 
Yes Yes Yes Yes 
Protective bonding 
resistance 200 mA (
) 
- - - - 
Protective bonding 
resistance 5 A (
) 
- - - - 
Insulation resistance 500 V 
(M
) 
2.00
2.00
- - 
Substitute leakage current 
(mA) 
- 0.50
-  - 
Protective conductor 
current (mA) 
- - - 
0.50
Touch current (mA) 
0.50
0.50
Apparent power (kVA) 
3.7 
3.7 
3.7