Honeywell 805595 Manuel D’Utilisation

Page de 46
IQ8Wireless transponder for wall mounting 
 
32 
FB 798941 / 10.06 
10 Installation 
10.1 
Connecting the power supply 
The power supply can come from the fire alarm control panel or from an external power unit. 
To supply power to the IQ8Wireless transponder you must install a separate, protected supply 
line. The connection cable must comply with the guidelines relating to the functions of fire 
alarm systems. If several IQ8Wireless transponders are connected to a shared power supply, 
each power line must be protected individually and non-reactively, for example with the 8-fuse 
card (Part No. 382040). 
 
Monitoring the power supply 
The external power supply is monitored by the wireless transponder. If the IQ8Wireless 
transponder is installed as a device on the analog loop of the IQ8Control fire alarm system, 
a fault is transmitted via the loop to the fire alarm control panel where it is displayed.  
 
If you connect the IQ8Wireless transponder to a standard detector zone, the >Common fault 
relay< (SaS-Stör) output may be used to report faults. 
 
 
-
+
U
B
-
+
9 V.....30 V DC
External Power supply
FACP
UB
ext.
GND
UB
ext.
GND
Fault
contact
or
 
Fig. 17: Power supply connection 
 
 
 
A VdS-approved power unit according to EN54-4 must be connected to supply 
power to the IQ8Wireless transponder, e.g. external 12 V DC power unit with 
battery compartment (Part No. 785653) or 24 V DC design (Part No. 785655).