Beckett CULUS CF1400 Manuel D’Utilisation

Page de 24
16
Figure 16 – Adjusting Plate Initial Setting, Typical
Table 4A – CF1400 Initial Indicator Adjustment Plate 
Settings
CF1400
Tube
Head Position
Damper Position
Approximate
Head Setting
Firing Rate
(gph)
Approximate
Air Damper 
Setting
Firing 
Rate (gph)
A
0
4.00
0
--
1
4.50
10
--
2
5.00
20
4.00
3
6.00
30
5.00
4
7.00
40
7.00
5
7.50
50
8.00
6
8.00
60
10.00
7 9.00
70
11.00
8
9.50
80
--
9
10.00
90
--
10
11.00
100
--
--
--
110
--
--
--
120
--
B
0
7.00
0
--
1
7.50
10
--
2
8.00
20
--
3
9.00
30
--
4
10.00
40
7.00
5
10.50
50
8.00
6
11.00
60
10.00
7 12.00
70
11.00
8
13.00
80
12.00
9
13.25
90
12.50
10
13.60
100
13.00
--
--
110
13.25
--
--
120
13.60
Table 4B – CF2300 Initial Indicator Adjustment Plate 
Settings
CF2300
Tube
Head Position
Damper Position
Approximate 
Head Setting
Firing Rate 
(gph)
Approximate 
Air Damper 
Setting
Firing 
Rate (gph)
A
0
11.0
0
--
1
12.0
10
7.0
2
13.0
20
10.0
3
14.0
30
13.0
4
15.0
40
14.0
5
16.0
50
15.0
6
17.0
60
16.0
7
18.0
70
17.0
8
19.0
80
18.0
9
20.0
90
19.0
--
--
100
20.0
B
0
12.5
0
--
1
13.0
10
10.0
2
14.0
20
13.0
3
15.0
30
14.0
4
16.0
40
15.0
5
17.0
50
16.0
6
18.0
60
17.0
7
18.5
70
18.0
8
19.0
80
18.5
9
20.0
90
19.0
--
--
100
20.0
Legend
b Spline nut for securing nozzle line
c Bottom acorn nut (for head adjustments)
d Top acorn nut (for setting dim. Z only - do not loosen 
after setting Z)
e Indicator adjusting plate
f Secondary adjusting plate
g Primary adjusting plate
h Copper oil line from oil valve to nozzle line
Initial Head Position
The indicator plate assembly (item 
e
) markings 
correspond to head position settings (Figure 16).
Slide the secondary adjusting plate (item 
f
) toward 
the rear of the burner until the number on the 
indicator plate corresponds to the initial head setting 
given in 
Tables 4a and 4b
 for the desired fi ring rate 
and burner (high-fi re).
Figure 16
 shows a typical example, with a head 
setting of 
6
.
When the head position has been set, tighten the 
bottom acorn nut (item 
c
) and the spline nut (item 
b
).
Section: Prepare the Burner for Start-up