Beckett CULUS CF1400 Manuel D’Utilisation

Page de 24
14
Figure 14 – Typical Wiring (R7184B)
Typical Burner Sequence of Operation - 
7184B Control
Refer to the appliance manufacturer’s wiring diagram for actual 
specifi cations.
Standby — The burner is idle, waiting for a call for heat. 
When a call for heat is initiated, there is a 3- to 10-second 
delay while the control performs a safe start check.
Valve-on delay — As applicable, the ignition and motor 
are turned on for a 15-second prepurge.
Trial for ignition (TFI) — The fuel valve is opened, as 
applicable. A fl ame should be established within the 15-
second lockout time (30-second lockout time is available).
Lockout — If fl ame is not sensed by the end of the TFI, 
the control shuts down on safety lockout and must be 
manually reset. If the control locks out three times in a 
row, the control enters restricted lockout. Call a qualifi ed 
service technician.
Ignition carryover — Once fl ame is established, the 
ignition remains on for 10 seconds to ensure fl ame 
stability. It then turns off.
Run — With a fl ame established and the control 
continuing to detect a fl ame, the burner will operate in the 
RUN Mode until the load demand is satisfi ed or a limit 
opens. 
If terminals RC1 and RC2 are jumpered, the burner 
operates in the Low-High-Off Mode. The burner starts 
at Low, goes to High after the fl ame stabilization 
1.
2.
3.
4.
5.
6.
a.
period. Flame is extinguished when the load is 
satisfi ed or a limit opens, and the burner is sent to 
Motor-Off Delay. 
If a high/low control has been wired between 
terminals RC1 and RC2 the burner starts at Low and 
is released to go High after the fl ame stabilization 
period. It can repeatedly cycle between low and high 
as necessary to meet load demand until the load is 
satisfi ed or a limit opens. The  burner is then sent to 
Motor-off Delay. 
Recycle — If the fl ame is lost while the burner is fi ring, 
the control shuts down the burner, enters a 60-second 
recycle delay, and then repeats the ignition steps outlined 
above. If the fl ame is lost three times in a row, the control 
locks out to prevent continuous cycling with repetitious 
fl ame loss caused by poor combustion.
Burner motor-off delay — The fuel valve is closed and 
the burner motor is kept on for the selected postpurge 
time before the control returns the burner to standby.
Cad Cell Resistance Indicator:  During the burner run 
state, click the reset button (less than 1 second) to check 
the cad cell resistance range.  The yellow light will fl ash 1 
to 4 times, depending on the amount of light detected by 
the cad cell.
See Figure 15 for Sequence of Operation illustration.
Restricted Lockout
If the control locks out three times in a row without a 
b.
7.
8.