CF1400/CF2300 Burner Manual
The fuel unit nozzle port pressure is factory set at 300 
psig. Some original equipment manufacturer burner 
applications may call for a lower pressure to obtain a 
required fi ring rate.  Do not change this pressure unless 
directed to do so by the appliance manufacturer.
Electrical Supply
Verify that the power connections available are correct 
for the burner. Refer to Figure 1.  All power must be 
supplied through fused disconnect switches.
Figure 1 – Typical Nameplate
Vent System
The fl ue gas venting system must be in good condition 
and must comply with all applicable codes.
Verify Burner Components
Burner nameplate (Figure 1), Model CF1400 or 
CF2300A
Air tube assembly
Mounting fl ange kit
Pedestal mounting assembly kit (recommended)
Oil nozzle, per Table 1 — Use only 45° to 70° 
solid pattern nozzles unless otherwise shown by 
appliance manufacturer or on the burner nameplate 
rating label.
Find the required fi ring rate in the 300 psig column (high 
fi re rate).  Select the corresponding nozzle from column 1 
(Rated gph @ 100 psig).
(Example: a 5.00 gph nozzle @ 300 psi = 8.66 gph)
Verify Firing Rate
Refer to appliance manufacturer’s instructions (if 
available) for fi ring rate and nozzle selection. Otherwise, 
the maximum recommended fi ring rate for the burner 
depends on the length of the fi ring chamber and the 
distance from the burner center to the chamber fl oor. 
Verify that the chamber dimensions are at least as 
large as the minimum values given in Figure 2. If the 
appliance dimensions are smaller than recommended, 
reduce the fi ring rate accordingly.



Table 1 – Nozzle Capacities
Rated 
gph 
@100 
psig
Pressure - Pounds per square inch
125
140
150
175
200
250
275
300
3.00
3.35
3.55
3.67
3.97
4.24
4.74
4.97
5.20
3.50
3.91
4.14
4.29
4.63
4.95
5.53
5.80
6.06
4.00
4.47
4.73
4.90
5.29
5.66
6.32
6.63
6.93
4.50
5.04
5.32
5.51
5.95
6.36
7.11
7.46
7.79
5.00
5.59
5.92
6.12
6.61
7.07
7.91
8.29
8.66
5.50
6.15
6.51
6.74
7.27
7.78
8.70
9.12
9.53
6.00
6.71
7.10
7.35
7.94
8.49
9.49
9.95
10.39
6.50
7.26
7.69
7.96
8.60
9.19
10.28
10.78
11.26
7.00
7.82
8.28
8.57
9.25
9.90
11.07
11.61
12.12
7.50
8.38
8.87
9.19
9.91
10.61
11.86
12.44
12.99
8.00
8.94
9.47
9.80
10.58
11.31
12.65
13.27
13.86
8.50
9.50
10.06
10.41
11.27
12.02
13.44
14.10
14.72
9.00
10.06
10.65
11.02
11.91
12.73
14.23
14.93
15.59
9.50
10.60
11.24
11.64
12.60
13.44
15.02
15.75
16.45
10.00
11.18
11.83
12.25
13.23
14.14
15.81
16.58
17.32
10.50
11.74
12.42
12.86
13.89
14.85
16.60
17.41
18.19
11.00
12.30
13.02
13.47
14.55
15.56
17.39
18.24
19.05
12.00
13.42
14.20
14.70
15.88
16.97
18.97
19.90
20.79
Section: Pre-Installation Checklist
LISTED
(FUEL) BURNER      NO.P100000
SERIAL NUMBER
050214-00000
Control Circ: 120V/60Hz 4.5A
Motor Circ: 120V/60Hz 4.0A
Model “XX”
Series (Fuel) Burner
R.W. Beckett Corp.
Elyria, Ohio
Made in the U.S.A.
For use with Group 8 . . . 
MP 1192      XX000      R00
X
X
X
X
X
X
XX000     R00
050214-00000
MFR’S SETTINGS
R.W. Beckett Construction & 
Setting Data
R.W. Beckett Specifi cation
Number and Revision
Boiler Manufacturer and 
Model, When Applicable
Additional Codes
General Model Information
Serial Number, Including Date Code
Rating Information
Approval Agency Symbols
Primary Group and Fuel