Beckett CULUS CF1400 Manuel D’Utilisation

Page de 24
7
CF1400/CF2300 Burner Manual
Stray Light
The control must detect a dark, no-fl ame condition 
in order to start the burner or it will hold in the stray 
light lockout mode.
Shield the burner view window from direct exposure 
to intense light. 
Mount the Burner
Mount Flange(s) on Air Tube
This section does not apply to burners with welded 
fl anges.
Do not install air tube on burner.
For non-pressure fi ring fl ange, refer to Figure 4:  
Install gasket (item a) and fl ange (item c). Ignore the 
next paragraph.
For pressure-fi ring fl ange, refer to Figure 4:  Slide 
gasket (item a) onto the air tube, making sure the 
top of the air tube is up. Predrill holes in the pressure 
fi ring plate (item b) to match the appliance studs. 
Slide the pressure fi ring plate (item b) and fl ange 
(item d) onto the air tube as shown. Wrap ceramic 
fi ber rope (not shown) around the air tube and press 
tightly into the inside diameter of the fl ange (item c).
Slide the air tube (item d) into position in the 
appliance front. Tighten the fl ange-mounting-stud 
nuts. Set the insertion of the air tube so dimension G 
is 1/4” nominal.
Pitch the air tube at 2° from horizontal as shown and 
secure the fl ange to the air tube. 

Dust and Moisture
Figure 4 – Mount fl ange(s) on air tube
Protect Against Stray Light 
Lockout  Failure to follow these 
instructions could cause loss of burner operation 
resulting in no heat, an unplanned process interruption, 
work stoppage and the potential for frozen plumbing or 
other cold weather property damage.
Protect Against Dust and 
Moisture 
Wet, dusty environments could lead to blocked 
air passages, corrosion damage to components, 
impaired combustion performance and result in 
asphyxiation, explosion or fi re.
This burner is designed for clean, dry installations.
Electrical controls are not protected against rain or 
sprayed water.
Keep the installation clear of dust, dirt, corrosive 
vapors, and moisture.
Protective covers and more frequent maintenance 
may be required.
y
y
y
y
Protect the air tube from 
overheating. 
Overheating could cause damage to the air tube and 
other combustion components leading  to equipment 
malfunction and impaired combustion performance.
The end of the air tube must not extend into the 
combustion chamber unprotected unless it has 
been factory-tested and specifi ed by the appliance 
manufacturer.
Position the end of the air tube 1/4” back from 
fl ush with the refractory inside entry wall to prevent 
damage from overheating
y
y
Section: Mount the Burner
Figure 3b - Firebox Pressure: CF2300 with no Reserve Air
0.2
0.4
0.6
0.8
1.0
0.0
18
17
16
15
Firebox Pressure in Inches Water Column (W.C.)
Maximum Firing Rate U.S. GPH
KS
KG
19
20
21
Figure 3a - Firebox Pressure: CF1400 with no Reserve Air
0.2
0.4
0.6
0.8
1.0
0.0
12
11
10
9
Firebox Pressure in Inches Water Column (W.C.)
Maximum Firing Rate U.S. GPH
KE
KD
13
14
15