Table 33.  FSCP override custom bindings 
Function
Originator
Network variable
Destination
supplyFanManControl
MP580-3
nvoPercent01
Mechanical system/nviPercent10
supplyDamperManFloor01
MP580-3
nvoPercent02
Mechanical system/nviPercent02
returnDamperManFloor01
MP580-3
nvoPercent03
Mechanical system/nviPercent03
supplyDamperManFloor02
MP580-3
nvoPercent04
Mechanical system/nviPercent04
returnDamperManFloor02
MP580-3
nvoPercent05
Mechanical system/nviPercent05
returnFanManControl
MP580-4
nvoPercent01
Mechanical system/nviPercent11
supplyDamperManFloor03
MP580-4
nvoPercent02
Mechanical system/nviPercent06
returnDamperManFloor03
MP580-4
nvoPercent03
Mechanical system/nviPercent07
supplyDamperManFloor04
MP580-4
nvoPercent04
Mechanical system/nviPercent08
returnDamperManFloor04
MP580-4
nvoPercent05
Mechanical system/nviPercent09
stairFanManControl
MP580-2
nvoPercent01
Mechanical system/nviPercent01