Trane TRACER SUMMIT BAS-APG001-EN Manuel D’Utilisation

Page de 156
Custom bindings
BAS-APG001-EN
129
UUKL binding list (actuator failure status)
Table 35 shows an example list of actuator failure status bindings. 
Actuator failure status is sent directly from the mechanical system to the 
FSCP. 
UUKL binding list (FSCP control)
Table 36 shows an example list of smoke control panel control custom 
bindings. Smoke control panel commands affect all MP581s panel control 
units.
Table 35.  Actuator failure status bindings 
Function
Originator
Network variable
Destination
supplyFanFail
Mechanical system
nvoSwitch20
MP580-3/nviSwitch05
returnFanFail
Mechanical system
nvoSwitch21
MP580-4/nviSwitch04
oadamperFail
Mechanical system
nvoSwitch22
MP580-3/nviSwitch03
radamperFail
 Mechanical system
nvoSwitch23
MP580-2/nviSwitch01
eadamperFail
 Mechanical system
nvoSwitch24
MP580-4/nviSwitch02
stairFanFail
Mechanical system
nvoSwitch25
MP580-2/nviSwitch02
supplyDamperFloor01Fail
Mechanical system
nvoSwitch26
MP580-3/nviSwitch07
returnDamperFloor01Fail
Mechanical system
nvoSwitch27
MP580-3/nviSwitch08
supplyDamperFloor02Fail
Mechanical system
nvoSwitch28
MP580-3/nviSwitch10
returnDamperFloor02Fail
Mechanical system
nvoSwitch29
MP580-3/nviSwitch11
supplyDamperFloor03Fail
Mechanical system
nvoSwitch30
MP580-4/nviSwitch06
returnDamperFloor03Fail
Mechanical system
nvoSwitch31
MP580-4/nviSwitch07
supplyDamperFloor04Fail
Mechanical system
nvoSwitch32
MP580-4/nviSwitch09
returnDamperFloor04Fail
 Mechanical system
nvoSwitch33
MP580-4/nviSwitch10
checkSupervisedCircuits
 Mechanical system
nvoSwitch40
MP580-2/nviSwitch04
Table 36.  Smoke control panel control custom bindings 
Function
Originator
Network variable
Destination
lampTest
 MP580-2
nvoSwitch01
MP580-3/nviSwitch40
nvoSwitch01
MP580-4/nviSwitch40
panel enable/disable
MP580-2
nvoSwitch03
MP580-3/nviSwitch36
nvoSwitch03
MP580-4/nviSwitch36